Side Access Replacement

This is the preferred replacement procedure.

1. Turn off the inverter input breaker.

2. Remove the side access panel.

3. With the proper tools, reach in and remove

the screws holding the surge suppression

assembly.

4. Replace the module with an Alpha service

entrance grade surge suppression

assembly.

Front Access Replacement

1. Turn off the inverter input breaker.

2. Remove the screw securing the CXCR unit.

3. Remove the 4 mounting screws that hold

the CXCR to the chassis.

4. Pull the CXCR out and to the left. Do not

remove any of the wires from the CXCR.

5. Dangle CXCR unit gently.

6. With the proper tools, reach in and remove

the bolts holding the surge suppression

assembly.

7. Replace the module with an Alphaservice

entrance grade surge suppression

assembly.

Bolts holding surge

suppression assembly

Bolts holding surge

suppression assembly

Advertising