6.3.10 Group Mapping

A matrix of buttons allows the supervisor to map (enable/disable) the inverter's assignment per group for all

of the acquired inverters in the system.

Power buttons – Green indicates an inverter is turned ON. An amber/orange/yellow color indicates the

inverter is in a recoverable error. The user can attempt to turn on the unit. The red color indicates the inverter

is in an irrecoverable error and there is nothing the user can do to turn on the unit. Black indicates an inverter

is manually OFF. Adding/removing groups (columns) may take a few seconds to incorporate the change.

Changing the radio style buttons (rows) will also take time to apply changes; for example, approximately two

seconds for one inverter and up to ten seconds for the maximum number of inverters (32).

If there are inverters mapped to a column, disabling a column is prevented and a warning message is dis-

played.

All inverters must be turned OFF to enable the AC Output Groups column buttons. The AC Output Groups of

an inverter in the ON state cannot be changed. The radio buttons for that inverter AC output group will remain

disabled until the inverter is turned OFF.

Figure 46 —

Group mapping window

Ensure phases are configured 

correctly before mapping invert-

ers in the new groups and turning

them on.

"Power Buttons"

Click these buttons to switch

the inverter ON/OFF. Use with

caution.

Green = inverter is ON

Black = inverter is OFF

Amber/Red = inverter ALARM