Alpha Technologies AMPS80 HP User Manual

Page 107

Advertising
background image

105

Doc. #: 026-069-B0 Rev F

;101;

;Remote OFF disable ACin Power;

;0; ; ;

x

0 –> Normal mode, default

x

1 –> ACin power is de-activated

;102;

;Negative Power (0 : OFF, 1 : ON);

;1; ; ;

x

1 –> ON, default

;103;

;External clock (0 : OFF, 1 : ON);

;0; ; ;

x

0 no in service protection

x

1 in service protection

;160;

;OUT 1 : phase shift (-180 to 360, default 0);

;0; ;deg;

;161;

;OUT 1 : Nominal Output Voltage (100 to 140);

;120; ;V;

x

Record of the phase shift and nominal Outlet voltage.

x

Phase shift range: -180 to 360, default: 0 deg

x

Nominal output voltage range: 100 to 140, default: 120 V

;170;

;OUT 2 : phase shift;

;120; ;deg;

;171;

;OUT 2 : Nominal Output Voltage;

;120; ;V;

x

Record the phase shift and the nominal Outlet voltage.

x

Range and defaults same as OUT 1

;180;

;OUT 3 : phase shift;

;240; ;deg;

;181;

;OUT 3 : Nominal Output Voltage;

;120; ;V;

x

Record the phase shift and the nominal Outlet voltage.

x

Range and defaults same as OUT 1

Parameters for DC Groups

;260;

;DC 1 : Vdc_in Low Start;

;49; ;V;

x

Low DC Voltage – a higher value causes the converter DC/AC to re-start

x

Range: 39 to 61, default: 49 V