Alpha Technologies AMPS80 HP User Manual

Page 26

Advertising
background image

Doc. #: 026-069-B0 Rev F

24

The recommendations in Table F are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table F — 20 kVA, split-phase, 2-pole systems (AMPS80-2-20 series),

single AC feed

Model

AMPS80-2-20

AMPS80-2-

20-H2

AMPS80-2-

20, MBS

AMPS80-2-

20-H2, MBS

AC

input

Feed

Single

Single

Single

Single

AC input voltage

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

Full load AC input current per phase

71 A

148 A

89 A

166 A

AC input poles & wiring

3 w + G

3 w + G

3 w + G

3 w + G

Wiring

2-pole

2-pole

2-pole

2-pole

Recommended

AC input breaker/fuse2

90 A

200 A

125 A

225 A

Recommended

AC input wire size

90ºC copper1

NEC 30ºC

#4

#2/0

#2

#3/0

CEC 30ºC

#3

#3/0

#2

#4/0

NEC 40ºC

#4

#2/0

#2

#3/0

CEC 40ºC

#3

#3/0

#2

#4/0

AC

output

Total maximum AC output

20 kVA, 16 kW

20 kVA, 16 kW

20 kVA, 16 kW

20 kVA, 16 kW

AC output voltage

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

120/208 V

or 120/240 V

AC output poles & wiring

3 w + G

3 w + G

3 w + G

3 w + G

Wiring

2-pole

2-pole

2-pole

2-pole

AC output current per phase

83 A

83 A

83 A

83 A

Installed inverter input

& output circuit breaker

125 A

125 A

125 A

125 A

Recommended

AC output wire size

90ºC copper1

NEC 30ºC

#2

#2

#2

#2

CEC 30ºC

#2

#2

#2

#2

NEC 40ºC

#1

#1

#1

#1

CEC 40ºC

#1

#1

#1

#1

AC input & output

connection terminals

Box lugs are rated for either Aluminum or Copper wire, 350 kcmil to #6 AWG. Fasten clamping screw

to 42 N-m (375 in-lbs) for #1 AWG to 350 kcmil wire or 23 N-m (200 in-lbs) for #6 to #2 AWG wire.

Note 1

Inverter AC Input & AC Output connections: Calculations based on full load and charging current, 0.8 derating with 5

current carrying conductors, (L1,L2,L3,2XN) due to possible high harmonic content load. Temperature correction factor

applied when needed.

Note 2

Maximum AC utility service protection feeding the AMPS80 HP is 400 A. The actual supply circuit breaker must be sized

appropriately for the supply wire used. Consult your local and national electrical codes. The AC source must be limited to 18 kA

short circuit current. Double neutral is strongly recommended for AC output wiring (and AC input wiring to the MBS) for 3Ф systems 

with significant non-linear (ie rectified capacitive) loads. Because the AC input to the inverters is power factor corrected, AC wiring 

solely to the inverters does not require double neutral wiring.

Advertising