6.3.12 Set Output

This submenu of Inverters will enable the supervisor to modify the following parameters:

Figure 48 —

Set Output window

For inverters,changes

apply on a page by

page basis; select

Submit

.

Select

Cancel

to

discard all changes

made (including

invalid settings).

An invalid setting (for any

configurable parameter) 

will be indicated with a

red exclamation mark.

Hovering the mouse on

the exclamation mark re-

veals the error message.

!

CAUTION!

The value entered in the Nominal Output Voltage field can change the actual AC output 

voltage of the inverters. Setting this value to anything other than 120 V will render the UL/

CSA approval invalid.

Number of Modules

Total number of inverter modules installed for that phase. Setting this number to

something different from the actual number of installed modules results in the

alarm condition

Inverter Comms Lost

.

Redundancy

Defines the number of inverter modules that will provide redundant power for that

phase (used to provide system warnings).

Phase shift

Assigns a phase shift (in degrees) to the AC output group.

Nominal Output Voltage

Enter

120

for all phases.

Ensure that the

Phase Shift

is set correctly before mapping inverters in the new groups and turning them on.