Alpha Technologies AMPS80 HP User Manual

Page 25

Advertising
background image

23

Doc. #: 026-069-B0 Rev F

The recommendations in Table E are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table E — 40 kVA, split-phase, 2-pole systems (AMPS80-2-40 series), dual AC feeds

Model

Dual feed with separate AC

feed for inverters/MBS and

rectifiers

AMPS80-2-40-H2

AMPS80-2-40-H2,

MBS

AC

input

AC feed

Inverter feed

Rectifier feed

Inverter/MBS feed

Rectifier feed

AC input voltage

120/208 V

or 120/240 V

208 V or 240 V

120/208 V

or 120/240 V

208 V

or 240 V

Full load AC input current per phase

148 A

77 A

179 A

77 A

AC input poles & wiring

3 w + G

3 w + G

3 w + G

3 w + G

Wiring

2-pole

2-pole

2-pole

2-pole

Recommended AC

input breaker/fuse2

200 A

100 A

225 A

100 A

Recommended

AC input wire size

90ºC copper1

NEC 30ºC

#2/0

#3

#3/0

#3

CEC 30ºC

#3/0

#3

#4/0

#3

NEC 40ºC

#2/0

#3

#3/0

#3

CEC 40ºC

#2/0

#3

#4/0

#3

AC

output

Total maximum AC output

40 kVA, 32 kW

40 kVA, 32 kW

AC output voltage

120/208 V or 120/240 V

20/208 V or 120/240 V

AC output poles & wiring

3 w + G

3 w + G

Wiring

2-pole

2-pole

AC output current per phase

167 A

167 A

Installed inverter input

& output circuit breaker

250 A

250 A

Recommended

AC output wire size

90ºC copper1

NEC 30ºC

#4/0

#4/0

CEC 30ºC

250 kcmil

250 kcmil

NEC 40ºC

250 kcmil

250 kcmil

CEC 40ºC

300 kcmil

300 kcmil

AC input & output

connection terminals

Box lugs are rated for either Aluminum or Copper wire, 350 kcmil to #6 AWG. Fasten clamping screw to

375 in-lbs (42 N-m) for #1 AWG to 350 kcmil wire or 200 in-lbs (23 N-m) for #6 to #2 AWG wire.

Rectifier connection

terminals

Box lugs are rated for either Aluminum or Copper wire, #2/0 to #6 AWG. Fasten clamping screw to 14

N-m (120 in-lbs)

Note 1

Inverter AC Input & AC Output connections: Calculations based on full load and charging current, 0.8 derating with 5

current carrying conductors, (L1,L2,L3,2XN) due to possible high harmonic content load. Temperature correction factor

applied when needed.

Note 2

Maximum AC utility service protection feeding the AMPS80 HP is 400 A. The actual supply circuit breaker must be sized

appropriately for the supply wire used. Consult your local and national electrical codes. The AC source must be limited to 18 kA short

circuit current. Double neutral is strongly recommended for AC output wiring (and AC input wiring to the MBS) for 3Ф systems with 

significant non-linear (ie rectified capacitive) loads. Because the AC input to the inverters is power factor corrected, AC wiring solely 

to the inverters does not require double neutral wiring.

Advertising