Table k — alarm codes – Alpha Technologies AMPS80 HP User Manual

Page 97

Advertising
background image

95

Doc. #: 026-069-B0 Rev F

Table K — Alarm Codes

Alarm Type

Description

Cause

Solution

230 REDUND + 1

LOST

Generate alarm code 230

and text "Redundancy + 1

Lost" when condition is true

Lost of inverter redundancy +

1 inverter

Replace defective inverter(s) or

adapt configuration

231 SYS

SATURATED

Generate alarm code 231

and text "Sys Saturated"

when the condition is true

Load of system is greater

than the preset value

Reduce load, or add inverter to

the system or reduce the number

of redundant units in Inverters >

Set Output, or change the alarm

level trigger.

232 MAIN SOURCE

LOST

Generate alarm code 232

and text "Mains source lost"

when the condition is true

Priority source lost (depends

on the configuration AC/AC 

or Online)

1) In AC/AC configuration: 

Reconnect AC IN or check

configuration or check live 

value. 2) In Online configuration: 

Reconnect DC or check

configuration or check level 

voltage

233 SEC SOURCE

LOST

Generate alarm code 233

and "Sec Source Lost"

when the condition is true

Secondary source

lost (depends on the

configuration AC/AC or 

Online)

1) In ONLINE configuration: 

reconnect AC IN or check

configuration or check live value. 

2) In AC/AC configuration: 

reconnect DC or check

configuration or check level 

voltage

234 T2S BUS FAIL Generate alarm code 234

and "T2S Bus Fail" when

the condition is true

The communication bus to

T2S has failed

Hardware problem. Replace T2S

235 T2S FAILURE Generate alarm code 235

and text "T2S Failure" when

the condition is true

T2S has failed

Hardware problem. Replace T2S

236 T2S STARTED Write event "T2S Started" in

log file when T2S is started 

(powered up)

T2S has started

237 LOG CLEARED Write event "Log Cleared"

in log file when the log is 

cleared

T2S has cleared the log

238 CONFIG

MODIFIED

Write event "Config 

Modified" in log file when 

configuration is modified.

Configuration is modified

239 NEW MOD

DETECTED

Write event "New Mod

Detected" in log file when 

new module is seen by T2S

One more module is plugged

240 DATE & TIME

MOD

Write event "Date & Time

Mod" in log file when date 

and/or time are modified

Date and time are modified

241 CFG READ IN

MOD

Write event "Cfg Read In

Mod" in log file when T2S 

had read the configuration 

file from TSI inverter. 

Tipically after insterting new

T2S on live system.

T2S has read the CFG

242 LOG

NEARLY FULL

Generate alarm code 242

and text "Log Nearly full"

when the condition is true

This item will be set as, No

alarm, Minor or major alarm.

(see configuration file)

Clear log file

243 T2S FLASH

ERROR

Flash of T2S is corrupt and

has failed

T2S failure

Hardware problem. Replace T2S