2 dc connection configurations – Alpha Technologies AMPS80 HP User Manual

Page 46

Advertising
background image

Doc. #: 026-069-B0 Rev F

44

Figure 24 —

DC connection dimensions – front view

5.3.2 DC Connection Configurations

CAUTION!

A tie bar is only recommended for single feed installations. The use of a tie bar in a two

feed installation can cause current loops.

If the system is equipped with optional rectifiers, each rectifier shelf in a hybrid system is only connected to

one of the DC- battery feeds:

• Top rectifier shelf to DC1
• Bottom rectifier shelf to DC4

In a system with four independent battery feeds, two of these battery banks will not be charged from the

AMPS80 HP rectifiers. When using two independent A/B feeds, DC1 should be tied to DC2 and DC3 tied to

DC4 at the AMPS80 HP DC connection points. Tie bars are provided.

[141]

8.9in

[227mm]

8.3in

3.0in

[76mm]

3.0in

[76mm]

5.4in

[137mm]

3.6in

[92mm]

3.6in [92mm]

3.0in

3.0in

[76mm]

Outside of right side

of AMPS system

Outside of left side

of AMPS system

DC+ ROW

DC- ROW

[211mm]

5.5

[76mm]

Top of

AMPS system

3.0in

[76mm]

7.4in

[187mm]

6.3in

[161mm]

3.0in

[76mm]

Advertising