1 ac or dc input priority – Alpha Technologies AMPS80 HP User Manual

Page 13

Advertising
background image

11

Doc. #: 026-069-B0 Rev F

AMPS modules also have a ‘Boost’ over-current feature with 10 times the rated current capacity for 20ms, al-

lowing it to trip breakers downstream, thus protecting the load.

2.1.1 AC or DC input priority

The user can choose either AC or DC input priority. If AC priority is chosen, the AMPS80 HP acts more

like an on-line, double conversion UPS. If AC commercial power is available, this power is filtered twice

and passed to the AC output. If the AC commercial power fails, the DC converter simply takes over and

supplies the power from the batteries.

If DC priority is chosen, the AMPS80 HP acts more like an Inverter with AC bypass function. Normally,

power is drawn from the batteries. If DC power fails, the AC-DC converter takes over, still providing regu-

lated and filtered power to the load.

DSP

400 Vdc

Boost

Telecom Grade

AC Output

DC In

AC

Mains

communication

CAN bus external

Dual redundant

synchronization

communication and

between modules

Advertising