Alpha Technologies AMPS80 HP User Manual

Page 53

Advertising
background image

51

Doc. #: 026-069-B0 Rev F

precise.)

a. Select Inverters > View Live Status> Inverter Report.

b. In the Inverter Report screen, locate the module for AC phase 1: click each row until the LEDs of the

inverter in the first phase 1 shelf flash for a few seconds.

c. Using the pull down box in the Module Number column, set the module number to 1 to correspond

to AC phase 1.

d. Locate the module for AC phase 2: click each row until the LEDs of the inverter in the first phase 2

shelf flash for a few seconds.

e. Use the pull down box to set the module number to 2 to correspond to AC phase 2 (for split phase,

2-pole and 3 phase systems).

f. Repeat for a third module (select 3 to correspond to AC phase 3) if the system is 3 phase.

21. Now that the inverter modules in each shelf have a number, place one module in each of the AC input

and output groups as follows:

Select a row to send a

Locate command; the in-

verter module LEDs will

flash for a few seconds.

Module number

pull down box

Figure 32 —

Inverters > View Live Status