Carefully review the following schematic and installation notes before proceeding with the installation.

Installation notes:

1. All wiring must be in accordance with applicable electrical codes.

2. All external wiring by others.

3. Inverter main input must always include a neutral connection.

4. Power and control cables must be in separate conduits.

5. N-G shorting jumper is factory-installed for inverter-only systems. Remove if AC input ground is

connected (#5 on Figure 19).

6. Where rectifier is fed separately from AC (#6 on Figure 19), remove these wires during installation—see

section 4.6.1.

7. L3 is only used with 3-phase systems.

8. Four independent battery strings can be connected. Shorting jumpers are provided for single or dual DC

feed ((#8 on Figure 19).

8

5

6

Figure 19 —

Battery and power connections

WARNING!

To maintain the security of all SELV Circuits in the AMPS80, connect to other equipment of

the same circuit type: signaling/alarm circuits, emergency power off (EPO) circuits, relay

contacts, Ethernet or CANBUS.