A6.5 lm parameters, A6.5.1 lm parameter list, A6.5 – Yokogawa EJX930A User Manual

Page 138: A6-4

Advertising
background image

<Appendix 6. Link Master Functions>

A6-4

IM 01C25R03-01E

A6.5 LM Parameters

A6.5.1 LM Parameter List

The tables below show LM parameters.

Meanings of Access column entries: RW = read/write possible; R = read only

Index

(SM)

Parameter Name

Sub-parameter Name

(Sub Index)

Default Factory

Setting

Access

Remarks

362 DLME_LINK_MASTER_CAPABILITIES_VARIABLE

0x04

RW

363 DLME_LINK_

MASTER_INFO_

RECORD

0

RW

1 MaxSchedulingOverhead

0

2 DefMinTokenDelegTime

100

3 DefTokenHoldTime

300

4 TargetTokenRotTime

4096

5 LinkMaintTokHoldTime

400

6 TimeDistributionPeriod

5000

7 MaximumInactivityToClaimLasDelay

2

8 LasDatabaseStatusSpduDistributionPeriod 6000

364 PRIMARY_LINK_MASTER_FLAG_VARIABLE

0

RW

LAS: True = 0xFF;

non-LAS: False = 0x00

365 LIVE_LIST_STATUS_ARRAY_VARIABLE

0

R

366 MAX_TOKEN_

HOLD_TIME_

ARRAY

0

RW

1 Element1

0

2 Element2

0

3 Element3

0

4 Element4

0

5 Element5

0

6 Element6

0

7 Element7

0

8 Element8

0

367 BOOT_OPERAT_FUNCTIONAL_CLASS

Specified at the time

of order

RW

0x01 (basic device);

0x02 (LM)

368 CURRENT_LINK_

SETTING_RECORD

0

R

Settings for LAS

1 SlotTime

0

2 PerDlpduPhlOverhead

0

3 MaxResponseDelay

0

4 FirstUnpolledNodeId

0

5 ThisLink

0

6 MinInterPduDelay

0

7 NumConseeUnpolledNodeId

0

8 PreambleExtension

0

9 PostTransGapExtension

0

10 MaxInterChanSignalSkew

0

11 TimeSyncClass

0

369 CONFIGURED_

LINK_SETTING_

RECORD

0

RW

1 SlotTime

4095

2 PerDlpduPhlOverhead

4

3 MaxResponseDelay

5

4 FirstUnpolledNodeId

37

5 ThisLink

0

6 MinInterPduDelay

12

7 NumConseeUnpolledNodeId

186

8 PreambleExtension

2

9 PostTransGapExtension

1

10 MaxInterChanSignalSkew

0

11 TimeSyncClass

4

Advertising