<9. Parameter Lists>

9-3

IM 01C25R03-01E

Relative

Index Index

Parameter Name

Factory Default

Write

Mode

Explanation

56

1056 SOFTDWN_ACT_

AREA

0

Indicates the ROM number of the currently working FlashROM.

0: FlashROM #0 working

1: FlashROM #1 working

57

1057 SOFTDWN_MOD_

REV

1, 0, 0, 0, 0, 0, 0,

0, 0

Indicates the software module revision.

58

1058 SOFTDWN_ERROR

0

Indicates the error during a software download.

Refer Table A7.4.

9.2 SENSOR Transducer Block

Relative

Index Index

Parameter Name

Factory Default

Write

Mode

Explanation

0

2000 Block Header

TAG: “STB”

Block

Tag=O/S

Information on this block such as Block Tag, DD Revision,

Execution Time etc.

1

2001 ST_REV

The revision level of the static data associated with the function

block. The revision value will be incremented each time a static

parameter value in the block is changed.

2

2002 TAG_DESC

Null

AUTO

The user description of the intended application of the block.

3

2003 STRATEGY

1

AUTO

The strategy field can be used to identify grouping of blocks.

This data is not checked or processed by the block.

4

2004 ALERT_KEY

1

AUTO

The identification number of the plant unit. This information may

be used in the host for sorting alarms, etc.

5

2005 MODE_BLK

AUTO

AUTO

The actual, target, permitted, and normal modes of the block.

6

2006 BLOCK_ERR

This parameter reflects the error status associated with

hardware or software components associated with a block. It is

a bit string, so that multiple errors may be shown.

7

2007 UPDATE_EVT

This alert is generated by any change to the static data.

8

2008 BLOCK_ALM

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the Active status in the Status attribute.

9

2009 TRANSDUCER_

DIRECTORY

A directory that specifies the number and starting indices of the

transducers.

10

2010 TRANSDUCER_TYPE 100 (Standard

Pressure with

Calibration)

Identifies transducer.

11

2011 XD_ERROR

The error code in transducer.

0=No failure

18=Calibration error

20=Electronics failure

22=I/O failure

12

2012 COLLECTION_

DIRECTORY

A directory that specifies the number, starting indices, and DD

Item Ids of the data collections in each transducer within a

transducer block.

13

2013 PRIMARY_VALUE_

TYPE

107: differential

pressure

O/S

The type of measurement represented by primary value.

14

2014 PRIMARY_VALUE

The measured value and status available to the function block.

15

2015 PRIMARY_VALUE_

RANGE

Range of capsule —

The High and Low range limit values, engineering units code

and the number of digits to the right of the decimal point to be

used to display the primary value.

16

2016 CAL_POINT_HI

Max range

O/S

The highest calibrated value.

17

2017 CAL_POINT_LO

0

O/S

The lowest calibrated value.

18

2018 CAL_MIN_SPAN

Minimum span of

capsule

The minimum calibration span value allowed.

19

2019 CAL_UNIT

kPa

The engineering unit for the calibrated values.

20

2020 SENSOR_TYPE

Silicon resonant

The type of sensor.

21

2021 SENSOR_RANGE

Range of capsule —

The High and Low range limit values, engineering units code

and the number of digits to the right of the decimal point for the

sensor.

22

2022 SENSOR_SN

Serial No.

Serial number.