<9. Parameter Lists>

9-12

IM 01C25R03-01E

9.5 Al Function Block

Relative

Index

Index

Parameter

Name

Factory

Default

Write

Mode

Explanation

AI1 AI2 AI3 AI4 AI5

0

4000 4100 4200 4300 4400 Block

Header

TAG:

“AI1” or “AI2” or

“AI3” or “AI4” or

“AI5”

Block Tag

= O/S

Information on this block such as Block Tag, DD

Revision, Execution Time etc.

1

4001 4101 4201 4301 4401 ST_REV

The revision level of the static data associated

with the function block. The revision value will be

incremented each time a static parameter value in

the block is changed.

2

4002 4102 4202 4302 4402 TAG_DESC Null

AUTO

The user description of the intended application of

the block.

3

4003 4103 4203 4303 4403 STRATEGY 1

AUTO

The strategy field can be used to identify grouping

of blocks. This data is not checked or processed by

the block.

4

4004 4104 4204 4304 4404 ALERT_

KEY

1

AUTO

The identification number of the plant unit. This

information may be used in the host for sorting

alarms, etc.

5

4005 4105 4205 4305 4405 MODE_BLK AUTO

AUTO

The actual, target, permitted, and normal modes of

the block.

6

4006 4106 4206 4306 4406 BLOCK_

ERR

This parameter reflects the error status associated

with the hardware or software components

associated with a block. It is a bit string, so that

multiple errors may be shown.

7

4007 4107 4207 4307 4407 PV

Either the primary analog value for use in executing

the function, or a process value associated with it.

May also be calculated from the READBACK value

of an AO block.

8

4008 4108 4208 4308 4408 OUT

Value=

MAN

The primary analog value calculated as a result of

executing the function.

9

4009 4109 4209 4309 4409 SIMULATE Disable

AUTO

Allows the transducer analog input or output to the

block to be manually supplied when simulate is

enabled. When simulation is disabled, the simulate

value and status track the actual value and status.

10

4010 4110 4210 4310 4410 XD_SCALE AI1, AI2, AI3:

Specified at the

time of order

AI4:

0 to 1000 kg/h

O/S

The high and low scale values, engineering units

code, and number of digits to the right of the

decimal point used with the value obtained from the

transducer for a specified channel.

11

4011 4111 4211 4311 4411 OUT_

SCALE

AI1, AI2, AI3:

Specified at the

time of order

AI4:

0 to 1000 kg/h

O/S

The high and low scale values, engineering units

code, and number of digits to the right of the decimal

point to be used in displaying the OUT parameter

and parameters which have the same scaling as

OUT.

12

4012 4112 4212 4312 4412 GRANT_

DENY

0

AUTO

Options for controlling access of host computers and

local control panels to operating, tuning and alarm

parameters of the block.

13

4013 4113 4213 4313 4413 IO_OPTS

0

O/S

Options which the user may select to alter input and

output block processing.

14

4014 4114 4214 4314 4414 STATUS_

OPTS

0

O/S

Options which the user may select in the block

processing of status.

15

4015 4115 4215 4315 4415 CHANNEL AI1: 1

AI2: 2

AI3: 4

AI4: 5

AI5: 6

O/S

The number of the logical hardware channel that is

connected to this I/O block. This information defines

the transducer to be used going to or from the

physical world.

1:PV 2:SV 3:TV 4:EXT_TEMP_VALUE

5:FLOW_VALUE 6:CAP_TEMP_VAL

7:AMP_TEMP_VAL 8:FLG_TEMP_VAL

16

4016 4116 4216 4316 4416 L_TYPE

AI1:

Specified at the

time of order

AI2 to AI5:

Direct

MAN

Determines if the values passed by the transducer

block to the AI block may be used directly (Direct) or

if the value is in different units and must be converted

linearly (Indirect), or with square root (Ind Sqr Root),

using the input range defined by the transducer and

the associated output range.