<Appendix 8. Advanced Diagnostics>

A8-2

IM 01C25R03-01E

Functional block diagram

The figure below shows the functional block diagram of ILBD, which is performed in the SENSOR Transducer

block.

block AI

Function block

block AI

Function block

EJX

(1)

(2)

(3)

(4)

(5)

(6)

FA0801.ai

Output of AI

Sensor

Sensor

signals

SENSOR

Transducer block

Process value

calculation

Blockage degree

Execution of

ILBD

Alarm

Masking

block AI

Function block

Add result of
blockage detection to status

Resource

block

LCD Transducer

block

Values of blockage degree

Result of

blockage detection

Result of

blockage detection

Blockage alarm

Blockage alarm

AI.OUT

STB.RATIO_FDP

STB.RATIO_FSPL

STB.RATIO_FSPH

STB.VALUE_FSPH

STB.VALUE_FSPL

STB.VALUE_FSPH

STB.VALUE_BLKF

RS.DEVICE_STATUS_7

STB.DIAG_ERR

STB.DIAG_H_ALM
STB.DIAG_L_ALM

Display on LCD

Figure A8.1 Functional Block Diagram of ILBD

The following outputs are given for the ILBD results.

Table A8.1 List of Outputs for ILBD

FA0802.ai

RATIO_FDP

The result of blockage detection can be set to “UNCERTAIN: Non Specific” if

DIAG_OPTION has been set to indicate the alarm status.
Parameters based on the fluctuation value and blockage degree

[

COMP_FLG: Non-Compensation ]

[ COMP_FLG: Compensation ]

When an impulse line blockage is detected, the result of the blockage detection

(alarm status) is indicated.
When an impulse line blockage is detected, the results of the blockage detection

(alarm status) are indicated.

When an impulse line blockage is detected, an alert is generated by divided into

high- and low-pressure sides.

Blockage degree characterized in comparison of high-pressure side and

low-pressure side pressure fluctuation value

When impulse line blockage is detected, an alarm status is displayed on LCD.

Average value of the sum of squares of differential pressure fluctuations

Average value of the sum of squares of high-pressure side static pressure fluctuation

Average value of the sum of squares of low-pressure side static pressure fluctuation

#

Parameter name

OUTPUT

Block

Remarks

AI function block

OUT

RATIO_FSPH

VALUE_BLKF

SENSOR

Transuducer Block

Resource block

DEVICE_STATUS_7

SENSOR

Transducer block
SENSOR

Transducer block

DIAG_ERR

DIAG_H_ALM

DIAG_L_ALM

VALUE_FDP
VALUE_FSPL
VALUE_FSPH

Display on LCD

(1)

(2)

(3)

(4)

(5)

(6)

=

RATIO_FDP

X REFERENCE_DPAVG

=

RATIO_FDP

VALUE_DPAVG

=

RATIO_FSPL

=

RATIO_FSPH

RATIO_FSPL

VALUE_FSPL

REFERENCE_FSPL

VALUE_FSPH

REFERENCE_FSPH

VALUE_FDP

REFERENCE_FDP

VALUE_FDP

REFERENCE_FDP