<5. Configuration>

5-6

IM 01C25R03-01E

Table 5.6

Link Object Parameters

Sub-

index

Parameter

Description

1

LocalIndex

Sets the index of function

block parameters to be

combined; set “0” for Trend

and Alert.

2

VcrNumber

Sets the index of VCR to be

combined. If set to “0”, this

link object is not used.

3

RemoteIndex

Not used in EJX. Set to “0”.

4

ServiceOperation Set one of the following.

Set only one each for link

object for Alert or Trend.

0: Undefined

2: Publisher

3: Subscriber

6: Alert

7: Trend

5

StaleCountLimit

Set the maximum number

of consecutive stale input

values which may be

received before the input

status is set to BAD. To

avoid the unnecessary

mode transition caused

when the data is not

correctly received by

subscriber, set this

parameter to “2” or more.

Set link objects as shown in Table 5.7.

Table 5.7

Factory-Settings of Link Objects

(example)

Index Link Object #

Factory Settings

30000

1

AI1.OUT → VCR#6

30001

2

Trend → VCR#5

30002

3

Alert → VCR#7

30003

4

AI2.OUT → VCR#9

30004

to

30039

5 to 40

Not used

5.6.2 Trend Object

It is possible to set the parameter so that the

function block automatically transmits Trend. EJX

multivariable transmitter has seven Trend objects,

six of which are used for Trend in analog mode

parameters and one is used for Trend in discrete

mode parameter. A single Trend object specifies the

trend of one parameter.
Each Trend object has the parameters listed in

Table 5.8. The first four parameters are the items

to be set. Before writing to a Trend object, it is

necessary to release the WRITE_LOCK parameter.

Table 5.8

Parameters for Trend Objects

Sub-

index

Parameter

Description

1

Block Index

Sets the leading index of the

function block that takes a

trend.

2

Parameter

Relative

Index

Sets the index of parameters

taking a trend by a value

relative to the beginning of

the function block. In the EJX

AI block, the following three

types of trends are possible.

7: PV

8: OUT

19: FIELD_VAL

3

Sample Type

Specifies how trends are

taken. Choose one of the

following 2 types:

1: Sampled upon execution

of a function block.

2: The average value is

sampled.

4

Sample Interval Specifies sampling intervals

in units of 1/32 ms. Set the

integer multiple of the function

block execution cycle.

5

Last Update

The last sampling time.

6 to

21

List of Status

Status part of a sampled

parameter.

21 to

37

List of Samples Data part of a sampled

parameter.

Seven trend objects are factory-set as shown Table

5.9.

Table 5.9

Trend Object are Factory-Set

Index

Parameters

Factory Settings

32000 to

32005

TREND_FLT.1 to

TREND_FLT.5

Not used.

32006 TREND_DIS.1

Not used.

F0505.ai

SMIB

(System

Management

Information

Base)

NMIB

(Network

Management

Information

Base)

AI1 OUT AI2 OUT

FBOD

Alert

Trend

VCR

DLSAP

DLCEP

Fieldbus Cable

EJX

0xF8 0xF3 0xF4 0xF7 0xF9 0x20 0x21 0x07

#1

#2

#3

#4

Resource

block

Transducer

block

Host 1

Host 2

Device 1

Device 2

Link

object

#1

#2 #3 #4

#5

#6

#7

#8

#9

Figure 5.5

Example of Default Configuration