<7. In-Process Operation>

7-2

IM 01C25R03-01E

7.3 Simulation Function

There are two simulation functions in EJX

multivariable transmitter; one is the function

commonly offered in F

OUNDATION

Fieldbus products

to simulate input of each function block for loop

check, and the other is the flow simulation function

to simulate measured inputs for checking the result

of flow calculation.
The simulation function described in this section is

the former one. For flow simulation function, see

‘6.3.6 Simulation Function.’
The simulation function simulates the input of a

function block and lets it operate as if the data was

received from the transducer block. It is possible to

conduct testing for the downstream function blocks

or alarm processes.
A SIMULATE_ENABLE switch is mounted in the

amplifier. This is to prevent the accidental operation

of this function. When this is switched on, simulation

is enabled. (See Figure 7.2.) To initiate the same

action from a remote terminal, if REMOTE LOOP

TEST SWITCH is written to the SIM_ENABLE_

MSG parameter (index 1044) of the resource block,

the resulting action is the same as is taken when

the above switch is on. Note that this parameter

value is lost when the power is turned OFF. In

simulation enabled status, an alarm is generated

from the resource block, and other device alarms

will be masked; for this reason the simulation must

be disabled immediately after using this function.
The SIMULATE parameter of AI block consists of

the elements listed in Table 7.2 below.

Table 7.2

SIMULATE Parameter

Subindex

Parameters

Description

1

Simulate Status

Sets the data status to

be simulated.

2

Simulate Value

Sets the value of the

data to be simulated.

3

Transducer Status Displays the data status

from the transducer

block. It cannot be

changed.

4

Transducer Value Displays the data value

from the transducer

block.It cannot be

changed.

5

Simulate

En/Disable

Controls the simulation

function of this block.

1: Simulation disabled

(standard)

2: Simulation started

When Simulate En/Disable in Table 7.2 above is

set to 2, the applicable function block uses the

simulation value set in this parameter instead of

the data from the transducer block. This setting can

be used for propagation of the status to the trailing

blocks, generation of a process alarm, and as an

operation test for trailing blocks.

F0702.ai

Amplifier Assembly

1
2

O

N

"OFF" during operation

Not in use

SIMULATE_ENABLE

Figure 7.2

SIMULATE_ENABLE Switch Position