<6. Explanation of Basic Items>

6-15

IM 01C25R03-01E

Scaling

OUT_SCALE

Filter

PV_FTIME

Cutoff

LOW_CUT

L_TYPE

Simulate

SIMULATE.

Transducer Value

SIMULATE.Enable

Simulate

SIMULATE.

Simulate Value

Scaling

XD_SCALE

FIELD_VAL.Value

IO_OPTS.Low cutoff

OUT_D_SEL

PV.Value

MODE_BLK.Actual

Alarms

LO, LO_LO

HI, HI_HI

/100

/100

Disable

Enable

Direct

Indirect

=0(Disable)

Auto

=1(Enable)

OUT

OUT_D

Ind.Sqr Root

F0608.ai

Figure 6.5

Diagram of the AI Functional Block

6.6.2 Block Mode

The Block modes permitted for the AI function

block are Automatic (Auto), Manual (Man), and

Out of Service (O/S). When the Block mode of RB

(Resource Block) is Out of Service (O/S), Actual

is Out of Service (O/S) even if Automatic (Auto) or

Manual (Man) is written to Target.

6.6.3 IO_OPTS

IO_OPTS is a parameter used to select whether

options regarding input and output signals should

be enabled or disabled. In the case of the AI

function block, the only available option is “Low

cutoff”. When enabling the low cut function for

outputs, set this option.

6.6.4 STATUS_OPT

STATUS_OPT is a parameter to select options

regarding the status of signals. The AI function

block offers four options: Propagate Fault Forward,

Uncertain if Limited, BAD if Limited, and Uncertain if

Man mode.
Propagate Fault Forward

If the status from the sensor is Bad, Device failure

or Bad, Sensor failure, propagate it to OUT without

generating an alarm. The use of these sub-statuses

in OUT is determined by this option. Through this

option, the user may determine whether alarming

(sending of an alert) will be done by the block or

propagated downstream for alarming.
Uncertain if Man mode

When the “Uncertain if Man” is enabled and the

Actual mode is Man, the OUT signal status should

be “Uncertain”.

6.6.5 OUT_D

OUT_D.value is “1” when the alarms selected by

OUT_D_SEL occur.
OUT_D.status is linked OUT.status. OUT_D.value

can be written the value form 0 to 15 when block

mode is O/S or MAN mode. The OUT_D_SEL

options are shown below.

High High Alarm (1):

OUT_D.value will be “1” when HI_HI alarm

occurs.

High Alarm (2):

OUT_D.value will be “1” when HI alarm

occurs.

Low Low Alarm (4):

OUT_D.value will be “1” when LO_LO alarm

occurs.

Low Alarm (8):

OUT_D.value will be “1” when LO alarm

occurs.