A6-9 – Yokogawa EJX930A User Manual

Page 143

Advertising
background image

<Appendix 6. Link Master Functions>

A6-9

IM 01C25R03-01E

Q3. On a segment where an EJX works as the

LAS, another device cannot be connected.

How come?

A3-1. Check the following bus parameters that

indicate the bus parameter as being the LAS

for the EJX and the capabilities of being the

LAS for the device that cannot be connected:

• V(ST), V(MID), V(MRD) of EJX:

ConfiguredLinkSettingsRecord (index 369)

• V(ST), V(MID), V(MRD) of problematic

device: DlmeBasicInfo

Then, confirm that the following conditions

are met:

EJX

Problematic

Device

V(ST)

>

V(ST)

V(MID)

>

V(MID)

V(MRD)

>

V(MRD)

A3-2. Check the node address of the problematic

device is not included in the V(FUN)+V(NUN)

of the EJX.

Q4. “AL.20” is kept shown on LCD.
The LAS does not exist or is not identified in the

fieldbus network, or the EJX is not able to establish

communication with the LAS.
A4-1. Check that the LAS is connected on the

network. When using the EJX as the LAS,

follow the steps described in section A6.3.

A4-2. Adjust the parameters of the LAS to that of

the EJX. Refer to section 5.2 for details.

LAS

EJX

V(ST)

>

V(ST) 4 or above

V(MID)

>

V(MID) 4 or above

V(MRD)

>

V(MRD) 12 or above

A4-3. Check that the correct Node Address is used

for the EJX. Refer to section 5.2 for details.

Confirm that the Node Address of EJX

should be out of the parameters of the LAS

of V (FUN) ~ V (FUN)+V (NUN)

Confirm that the Node Address is not within

the default address (0xF8 to 0xFB).

Advertising