<9. Parameter Lists>

9-13

IM 01C25R03-01E

Relative

Index

Index

Parameter

Name

Factory

Default

Write

Mode

Explanation

AI1 AI2 AI3 AI4 AI5

17

4017 4117 4217 4317 4417 LOW_CUT Linear: 0%

Square root:

10%

AUTO

Limit used in square root processing. A value of zero

percent of scale is used in block processing if the

transducer value falls below this limit. This feature

may be used to eliminate noise near zero for a

flow sensor. The setting is in an engineering unit of

OUT_SCALE.

18

4018 4118 4218 4318 4418 PV_FTIME 0 (s)

AUTO

Time constant of a single exponential filter for the PV,

in seconds.

19

4019 4119 4219 4319 4419 FIELD_VAL —

Raw value of the field device in percent of the

PV range, with a status reflecting the Transducer

condition, before signal characterization (L_TYPE) or

filtering (PV_FTIME).

20

4020 4120 4220 4320 4420 UPDATE_

EVT

This alert is generated by any change to the static

data.

21

4021 4121 4221 4321 4421 BLOCK_

ALM

The block alarm is used for all configuration,

hardware, connection failure or system problems

in the block. The cause of the alert is entered in the

subcode field. The first alert to become active will

set the Active status in the Status attribute. As soon

as the Unreported status is cleared by the alert

reporting task, another block alert may be reported

without clearing the Active status, if the subcode has

changed.

22

4022 4122 4222 4322 4422 ALARM_

SUM

Enable

The current alert status, unacknowledged states,

unreported states, and disabled states of the alarms

associated with the function block.

23

4023 4123 4223 4323 4423 ACK_

OPTION

0xFFFF

AUTO

Selection of whether alarms associated with the

block will be automatically acknowledged.

24

4024 4124 4224 4324 4424 ALARM_

HYS

0.5%

AUTO

Amount the PV must return within the alarm limits

before the alarm condition clears. Alarm Hysteresis is

expressed as a percent of the PV span.

25

4025 4125 4225 4325 4425 HI_HI_PRI 0

AUTO

Priority of the high high alarm.

26

4026 4126 4226 4326 4426 HI_HI_LIM +INF

AUTO

The setting for high high alarm in engineering units.

27

4027 4127 4227 4327 4427 HI_PRI

0

AUTO

Priority of the high alarm.

28

4028 4128 4228 4328 4428 HI_LIM

+INF

AUTO

The setting for high alarm in engineering units.

29

4029 4129 4229 4329 4429 LO_PRI

0

AUTO

Priority of the low alarm.

30

4030 4130 4230 4330 4430 LO_LIM

–INF

AUTO

The setting for the low alarm in engineering units.

31

4031 4131 4231 4331 4431 LO_LO_PRI 0

AUTO

Priority of the low low alarm.

32

4032 4132 4232 4332 4432 LO_LO_LIM –INF

AUTO

The setting of the low low alarm in engineering units.

33

4033 4133 4233 4333 4433 HI_HI_ALM —

The status for high high alarm and its associated

time stamp.

34

4034 4134 4234 4334 4434 HI_ALM

The status for high alarm and its associated time

stamp.

35

4035 4135 4235 4335 4435 LO_ALM

The status of the low alarm and its associated time

stamp.

36

4036 4136 4236 4336 4436 LO_LO_

ALM

The status of the low low alarm and its associated

time stamp.

37

4037 4137 4237 4337 4437 OUT_D_

SEL

0

Selection of alarm to output it from OUT_D.

38

4038 4138 4238 4338 4438 OUT_D

Value=

MAN

A discrete value and status that shows HI_HI, HI,

LO_LO, LO state.