<Appendix 8. Advanced Diagnostics>

A8-20

IM 01C25R03-01E

Checklist (4/5)

No.

Items

Parameters

Result

Example

10-a-2 Low Side Blocking

• Close the low-pressure side valve

completely.

• Record the values of VALUE_# after

the certain time, (DIAG_PERIOD ×

DIAG_COUNT), passed.

*: Record the value after checked that

the status is “GOOD”.

VALUE_FDP (Index: 2103) *

7.48562e-9

VALUE_FSPL (Index: 2104) *

7.23277e-9

VALUE_FSPH (Index: 2105)

7.14085e-9

VALUE_BLKF (Index: 2106) *

-0.287259

• Record the status of Checkbox in

DIAG_OPTION.

• Check that the alarms status of “A

Blocking” and “Low Side Blocking” are

set.

Note: If the alarm of “Outside Diagnosis

Range” is generated, the valve may

be closed too much tightly. Open

valve a little and record the updated

status of the parameters.

DIAG_OPTION (Index: 2089)

A Blocking

Large Fluctuation of Low Side

Large Fluctuation of High Side

Low Side Blocking

High Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fDP

Outside Diagnosis Range

Reflect Blockage to PV/SV/TV

Status

• Check that the alarm of “Low Side

Blocking” is generated.

• Check that the alarm of “High Side

Blocking” is not generated.

DIAG_ERR (Index: 2086)

Low Side Blocking

High Side Blocking

10-a-3 Both Side Blocking

• Close the both-pressure side valves

completely.

• Record the values of VALUE_# after

the certain time, (DIAG_PERIOD ×

DIAG_COUNT), passed.

*: Record the value after checked that

the status is “GOOD”.

VALUE_FDP (Index: 2103)

7.48562e-9

VALUE_FSPL (Index: 2104)

7.23277e-9

VALUE_FSPH (Index: 2105)

7.14085e-9

VALUE_BLKF (Index: 2106)

-0.287259

• Record the status of Checkbox in

DIAG_OPTION.

• Check that the alarms status of “High

Side Blocking” , “Low Side Blocking”

and “B Blocking” are set.

Note: If the alarm of “Outside Diagnosis

Range” is generated, the valve may

be closed too much tightly.

Open valve a little and record the

updated status of the parameters.

DIAG_OPTION (Index: 2089)

A Blocking

Large Fluctuation of Low Side

Large Fluctuation of High Side

Low Side Blocking

High Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fDP

Outside Diagnosis Range

Reflect Blockage to PV/SV/TV

Status

• Check that the alarm of “B Blocking” is

generated.

DIAG_ERR (Index: 2086)

B Blocking