<Appendix 8. Advanced Diagnostics>

A8-19

IM 01C25R03-01E

Checklist (3/5)
Go to the following step according to the result of "Invalid Ref xx" shown in the DIAG_ERR of 8th check item.

DIAG_ERR (Index: F2086)

Check item

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fdP

10-a

10-b

: The alarm is generated.

: The alarm is not generated.

No.

Items

Parameters

Result

Example

10-a

Simulation of Blockage detection

operation

• High Side Blocking: 10-a-1

• Low Side Blocking: 10-a-2

• Both Side Blocking: 10-a-3

10-a-1 High Side Blocking

• Close the high-pressure side valve

completely.

• Record the values of VALUE_# after

the certain time, (DIAG_PERIOD ×

DIAG_COUNT), passed.

*: Record the value after checked that

the status is “GOOD”.

VALUE_FDP (Index: 2103)*

7.48562e-9

VALUE_FSPL (Index: 2104) *

7.23277e-9

VALUE_FSPH (Index: 2105) *

7.14085e-9

VALUE_BLKF (Index: 2106)

-0.287259

• Record the status of Checkbox in

DIAG_OPTION.

• Check that the alarms status of “A

Blocking” and “High Side Blocking”

are set.

Note: If the alarm of “Outside Diagnosis

Range” is generated, the valve may

be closed too much tightly. Open

valve a little and record the updated

status of the parameters.

DIAG_OPTION (Index: 2089)

A Blocking

Large Fluctuation of Low Side

Large Fluctuation of High Side

Low Side Blocking

High Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fDP

Outside Diagnosis Range

Reflect Blockage to PV/SV/TV

Status

• Check that the alarm of “High Side

Blocking” is generated.

• Check that the alarm of “Low Side

Blocking” is not generated.

DIAG_ERR (Index: 2086)

High Side Blocking

Low Side Blocking