<7. In-Process Operation>

7-1

IM 01C25R03-01E

7. In-Process Operation

This chapter describes the procedure performed

when changing the operation of the function block

of the EJX multivariable transmitter in process.

7.1 Mode Transition

When the function block mode is changed to

Out_Of_Service, the function block pauses and a

block alarm is issued.
When the function block mode is changed to

Manual, the function block suspends updating of

output values. In this case alone, it is possible to

write a value to the OUT parameter of the block

for output. Note that no parameter status can be

changed

7.2 Generation of Alarm

7.2.1 Indication of Alarm

When the self-diagnostics function indicates that a

device is faulty, an alarm (device alarm) is issued

from the resource block. When an error (block

error) is detected in each function block or an error

in the process value (process alarm) is detected, an

alarm is issued from each block. If an LCD indicator

is installed, the error number is displayed as AL.XX.

If two or more alarms are issued, multiple error

numbers are displayed.
For details of ALARM, refer to Section 8.2

F0701.ai

Figure 7.1

Error Identification on Indicator

7.2.2 Alarms and Events

The following alarms or events can be reported by

the EJX multivariable transmitter if Link object and

VCR static entry are set.
Analog Alerts (Generated when a process value

exceeds threshold)

By AI Block Hi-Hi Alarm, Hi Alarm, Low Alarm,

Low-Low Alarm

Discret Alerts (Generated when an abnormal

condition is detected)

By Resource Block Block Alarm, Write Alarm

By Transducer Block Block Alarm,

Diagnostic Alarm(option code: /DG1)

By AI, SC, IT, IS, AR and PID Blocks

Block Alarm

Update Alerts (Generated when an important

(restorable) parameter is updated)

By Resource Block Update Event

By Transducer Block Update Event

By AI, SC, IT, IS, AR and PID Blocks

Update Event

An alert has following structure:

Table 7.1

Alert Object

Subindex

Parameter

Name

Explanation

A

na

lo

g

A

le

rt

D

is

cr

et

e

A

le

rt

U

pd

at

e

A

le

rt

1

1

1 Block

Index

Index of block from which

alert is generated

2

2

2 Alert Key

Alert Key copied from the

block

3

3

3 Standard

Type

Type of the alert

4

4

4 Mfr Type

Alert Name identified by

manufacturer specific DD

5

5

5 Message

Type

Reason of alert

notification

6

6

6 Priority

Priority of the alarm

7

7

7 Time

Stamp

Time when this alert is

first detected

8

8

Subcode

Enumerated cause of this

alert

9

9

Value

Value of referenced data

10

10

Relative

Index

Relative index of

referenced data

8 Static

Revision

Value of static revision

(ST_REV) of the block

11

11

9 Unit Index Unit code of referenced

data