<6. Explanation of Basic Items>

6-1

IM 01C25R03-01E

6. Explanation of Basic Items

6.1 Outline

This chapter describes the SENSOR transducer

block, the LCD transducer block, and the AI function

block and explains basic parameter settings.

Refer to Appendixes for other function blocks, LM

function, and software download function.

6.2 Setting and Changing

Parameters for the Whole

Process

IMPORTANT

Do not turn off the power immediately after

setting. When the parameters are saved to the

EEPROM, the redundant processing is executed

for an improvement of reliability. If the power

is turned off within 60 seconds after setting is

made, the modified parameters are not saved

and the settings may return to the original values.

Block mode
Many parameters require a change of the block

mode of the function block to O/S (Out of Service)

when their data is changed. To change the block

mode of the function block, its MODE_BLK needs

to be changed. The MODE_BLK is comprised of

the four sub-parameters below:

(1) Target (Target mode):

Sets the operating condition of the block.

(2) Actual (Actual mode):

Indicates the current operating condition.

(3) Permit (Permitted mode):

Indicates the operating condition that the

block is allowed to take.

(4) Normal (Normal mode):

Indicates the operating condition that the

block will usually take.

6.3 SENSOR Transducer Block

The SENSOR transducer block is in between the

sensor and the AI function blocks. It calculates

differential pressure, static pressure, external

temperature, and capsule temperature from sensor

signals. Then it performs damping and range

checks for the measured values of these three

variables and sends signals to the AI function block

and Flow transducer block. Figure 6.1 presents the

signal flow between blocks.

F0601.ai

Sensor Transducer Block

PRIMARY_VALUE [DP]

(Channel1)

SECONDARY_VALUE [SP-H]

(Channel2)

TERITARY_VALUE [SP-L]

(Channel3)

EXT_TEMP_VAL

(Channel4)

CAP_TEMP_VAL

(Channel6)

AMP_TEMP_VAL

(Channel7)

FLG_TEMP_VAL

(Channel8)

Flow Transducer Block

FLOW_VAL

(Channel5)

AI Function Block

CHANNEL=?

AI

AI

AI

AI

Figure 6.1

Signal Flow Diagram