Yokogawa EJX930A User Manual

Page 84

Advertising
background image

<10. General Specifications>

10-3

IM 01C25R03-01E

Item

Description

Code

Canadian

Standards

Association

(CSA)

CSA Explosionproof

*2

Certificate: 2014354

Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,

C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1-01

Explosion-proof for Class I, Groups B, C and D.

Dustignition-proof for Class II/III, Groups E, F and G.

When installed in Division 2, “SEAL NOT REQUIRED” Enclosure: TYPE 4X, Temp. Code:

T6...T4

Ex d IIC T6...T4 Enclosure: IP66 and IP67

Max.Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)

Amb.Temp

*1

.: –50 to 75°C (–58 to 167°F) for T4, –50 to 80°C (–58 to 176°F) for T5,

–50 to 75°C (–58 to 167°F) for T6

CF1

CSA Intrinsically Safe

*3

IECEx

Scheme

*2

IECEx Flameproof

Applicable Standard: IEC 60079-0:2004, IEC60079-1:2003

Certificate: IECEx CSA 07.0008

Flameproof for Zone 1, Ex d IIC T6...T4 Enclosure: IP66/IP67

Max.Process Temp.: T4; 120°C (248°F), T5; 100°C (212°F), T6; 85°C (185°F)

Amb.Temp

*1

.: –50 to 75°C (–58 to 167°F) for T4, –50 to 80°C (–58 to 176°F) for T5,

–50 to 75°C (–58 to 167°F) for T6

SF2

*1:

Lower limit of ambient temperature shall be -15ºC (5ºF) when /HE is specified.

*2:

Applicable for electrical connection code

2, 4, 7, 9, C and D.

*3:

Pending.

< Factory Setting >

Tag Number (Tag plate)

As specified in order

Software Tag (PD_TAG)

‘FT1001’ unless otherwise both Tag Number and Software Tag

specified in order

Node Address

‘0xF5’ unless otherwise specified in order

Operation Functional Class

‘BASIC’ or as specified

Primary value

*1

Output Mode (L_TYPE)

‘Direct’ unless otherwise specified in order

Calibration Range (XD_SCALE)

Lower/Higher Range Value

As specified in order

Calibration Range Unit

Selected from mmH

2

O, mmH

2

O(68°F), mmHg, Pa, hPa, kPa,

MPa, mbar, bar, gf/cm

2

, kgf/cm

2

, inH

2

O, inH

2

O(68°F), inHg, ftH

2

O,

ftH

2

O(68°F) or psi. (Only one unit can be specified)

Output Scale (OUT_SCALE)

Lower/Higher Range Value

‘0 to 100%’ unless otherwise specified.

Software Damping

*2

‘2 seconds’ or as specified in order

Static pressure display range

‘0 to 25 MPa’ for EJX910A M and H capsule and ‘0 to 16 MPa’ for

EJX910A L capsule, absolute value.

‘0 to 32 MPa’ for EJX930A. Measuring high pressure side.

*1:

Primary means differential pressure in case of differential pressure transmitters and pressure in case of pressure transmitters.

*2:

To specify this item, /CC option is required.