<Appendix 8. Advanced Diagnostics>

A8-9

IM 01C25R03-01E

Invalid Ref BlkF, fSPh, fSPl, or fDP

This alarm indicates that the reference value under

normal condition is invalid. If REFERENCE_BLKF

is invalid, the blockage detection excluding VALUE_

BLKF is carried out. If blockage detection function

based on VALUE_BLKF is required, obtain the

reference value again.
Also when REFERENCE_DPAVG is below DIAG_

LIM [10] or exceeds DIAG_LIM [9], all reference

value becomes invalid so that “Invalid Ref fDP”,

“Invalid Ref fSPl”, “Invalid Ref fSPh”, and “Invalid

Ref BlkF” are generated.

Alarm Masking

DIAG_OPTION

The alarms linked to an analog alert and LCD

display are selected by DIAG_OPTION in the

SENSOR Transducer block. The BIT of DIAG_

OPTION is corresponding to that of DIAG_ERR.
To link the alarm to an analog alert and LCD display,

follow the procedure below.

1) Set "Stop" to DIAG_MODE.

2) Check each checkbox of the alarm, which is

selectable from bit 2 to bit 14.

Note: The bit 13 and 14 are used for Heat trace monitoring

function.

Set to “Calculation” after setting the parameters.

Analog Alert Setting

Link to DIAG_H_ALM and DIAG_L_ALM

DIAG_H_ALM and DIAG_L_ALM enable to indicate

the alarm status separately divided into the high-

and low-pressure-side alert. The factory setting is

not enabled to display them.
Enable to display the alarm status to DIAG_H_ALM

and DIAG_L_ALM according to the following

procedure.

1) Set "Stop" to DIAG_MODE.

2) Uncheck the checkbox of "Diag Alm Disabled”,

which is corresponding to bit 8, in ALARM_

SUM.

Note: Set to “Calculation” after setting the parameters.

Report Setting

DIAG_PRI in SENSOR Transducer block defines

the priority to transfer the analog alert to the host.

The alert is generated according to the priority when

interfering in other EJX alerts.

DIAG_PRI

Bit

Description

0

An alert is not generated.

1

An alert does not be reported to the host.

2

Disabled

3-7 ADVISORY

8-15 CRITICAL

The default value at the factory setting is set to 1.
Set the priority according to the following procedure.

1) Set "Stop" to DIAG_MODE.

2) Enter the value to DIAG_PRI in the number of 3

to 15.

Note: The setting of the highest priority is 15.

Set to “Calculation” after setting the parameters.

Alarm Display on LCD

If the ILBD algorithm detects the abnormality, the

content of the detected result is displayed with

“AL.88” or “AL.89” on the LCD. “AL.88” indicates

that condition is not applicable for the abnormality

detection and “AL.89” indicates the abnormality is

detected.

FA0808.ai

Figure A8.6 Display Example of High Side Blocking

The alarm display on LCD regarding ILBD is

described in Table 8.12 of the section 8.

Reflect Blockage to PV/SV/TV Status

“Reflect Blockage to PV/SV/TV Status”

corresponding to bit 15 in DIAG_OPTION is

used to link the alarm to the OUT signal status of

PRIMARY_VALUE, SECONDARY_VALUE, and

TERTIARY_VALUE.
When the ILBD algorithm detects the abnormality,

each signal status becomes “UNCERTAIN: Non

Specific”.
The alarm is linked to the signal status of PV, SV

and TV, according to the following procedure.

1) Set "Stop" to DIAG_MODE.

2) Check the checkbox of “Availability for the

Status” of DIAG_OPTION.

Note:Set to “Calculation” after setting the parameters.