A8-4 – Yokogawa EJX930A User Manual

Page 154

Advertising
background image

<Appendix 8. Advanced Diagnostics>

A8-4

IM 01C25R03-01E

High/Low Side Blocking Detection

EJX differential pressure transmitter enables

to detect both-, a high-, or low-pressure-side

blockage. The blockage degree characterized

by a comparison of high-pressure side and low-

pressure-side fluctuation values, VALUE_BLKF, is

used to detect it. The value changes within a range

of –1 to +1. As VALUE_BLKF approaches +1, the

high-pressure-side blockage progresses. On the

other hand, if it approaches -1, the low-pressure-

side blockage progresses.

1

0

1

0

FA0803.ai

VALUE_BLKF

Blockage detection for

high-pressure side

Threshold

Blockage Progress

VALUE_BLKF

Blockage detection for

low-pressure side

Threshold

Blockage Progress

-1

-1

Figure A8.2 Relation between Blockage Progress

and VALUE_BLKF

The each threshold value to detect the high- or

low-pressure-side blockage is set to DIAG_LIM [7]

or [8].

Low Side Blocking Detection

VALUE_BLKF is preferentially used to "Low Side

Blocking" detection. If VALUE_BLKF cannot

be used, RATIO_FSPL, SQRT (VALUE_FSPL

/ REFERENCE_FSPL) is used to "Low Side

Blocking" detection. REFERENCE_FSPL is

the average value of the sum of squares of low-

pressure-side static pressure fluctuations under

normal condition. As the value of RATIO_FSPL

is below the value of DIAG_LIM [4], EJX gives an

alarm of "Low Side Blocking". On the other hand, if

this value exceeds the value of DIAG_LIM [3], EJX

gives an alarm of “Large Fluctuation of Low Side”.

High Side Blocking Detection

VALUE_BLKF is preferentially used to "High

Side Blocking" detection. If VALUE_BLKF cannot

be used, RATIO_FSPH, SQRT (VALUE_FSPH

/ REFERENCE_FSPH) is used to "High Side

Blocking" detection. REFERENCE_FSPH is the

average value of the sum of squares of high-

pressure-side static pressure fluctuations under

normal condition.
As the value of RATIO_FSPH is below the value

of DIAG_LIM [6], EJX gives an alarm of "High Side

Blocking". On the other hand, if this value exceeds

the value of DIAG_LIM [5], EJX gives an alarm of

“Large Fluctuation of High Side”.

Large Fluctuation Detection

When a pump or compressor starts, the large

fluctuation is generated as process condition

changes rapidly. This phenomenon affects process

fluctuation measurement, so correct blockage

detection is not performed.
If “Large fluctuation of Low Side” or “Large

fluctuation of High Side” is detected, consider

whether a blockage result is correct.
The threshold values to detect large fluctuation are

set to DIAG_LIM [3] and [5].
Since these values are enough to detect large

fluctuation, it is not almost necessary to change

them.