Yokogawa EJX930A User Manual

Page 66

Advertising
background image

<9. Parameter Lists>

9-2

IM 01C25R03-01E

Relative

Index Index

Parameter Name

Factory Default

Write

Mode

Explanation

22

1022 MEMORY_SIZE

0

Available configuration memory in the empty resource. To be

checked before attempting a download.

23

1023 NV_CYCLE_T

0

Interval between writing copies of nonvolatile parameters to

non-volatile memory. Zero means never.

24

1024 FREE_SPACE

0

Percent of memory available for further configuration. EJX has

zero which means a preconfigured resource.

25

1025 FREE_TIME

0

Percent of the block processing time that is free to process

additional blocks. EJX does not support this.

26

1026 SHED_RCAS

640000 (2S)

AUTO

Time duration at which to give up on computer writes to function

block RCas locations. Supported only with PID function.

27

1027 SHED_ROUT

640000 (2S)

AUTO

Time duration at which to give up on computer writes to function

block ROut locations. Supported only with PID function.

28

1028 FAULT_STATE

1

Condition set by loss of communication to an output block,

failure promoted to an output block or a physical contact. When

fail-safe condition is set, then output function blocks will perform

their FSAFE actions.

29

1029 SET_FSTATE

1

AUTO

Allows the fail-safe condition to be manually initiated by

selecting Set.

30

1030 CLR_FSTATE

1

AUTO

Writing a Clear to this parameter will clear the device fail-safe

state if the field condition, if any, has cleared.

31

1031 MAX_NOTIFY

3

Maximum number of unconfirmed notify messages possible.

32

1032 LIM_NOTIFY

3

AUTO

Maximum number of unconfirmed alert notify messages

allowed.

33

1033 CONFIRM_TIM

5000 (ms)

AUTO

The minimum time between retries of alert reports.

34

1034 WRITE_LOCK

Not locked

AUTO

If set, no writes from anywhere are allowed, except to clear

WRITE_LOCK. Block inputs will continue to be updated.

1: Not Locked

2: Locked

35

1035 UPDATE_EVT

This alert is generated by any change to the static data.

36

1036 BLOCK_ALM

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the Active status in the Status attribute.

As soon as the Unreported status is cleared by the alert

reporting task, another block alert may be reported without

clearing the Active status, if the subcode has changed.

37

1037 ALARM_SUM

Enable

The current alert status, unacknowledged states, unreported

states, and disabled states of the alarms associated with the

function block.

38

1038 ACK_OPTION

0xFFFF

AUTO

Selection of whether alarms associated with the block will be

automatically acknowledged.

39

1039 WRITE_PRI

0

AUTO

Priority of the alarm generated by clearing the write lock.

40

1040 WRITE_ALM

This alert is generated if the write lock parameter is cleared.

41

1041 ITK_VER

5

Version number of interoperability test by Fieldbus Foundation

applied to EJX multivariable transmitter.

42

1042 SOFT_REV

EJX multivariable transmitter software revision number.

43

1043 SOFT_DESC

Yokogawa internal use.

44

1044 SIM_ENABLE_MSG

Null

AUTO

Software switch for simulation function.

45

1045 DEVICE_STATUS_1

0

Device status For details, refer to Table 8.1

46

1046 DEVICE_STATUS_2

0

Device status For details, refer to Table 8.2

47

1047 DEVICE_STATUS_3

0

Device status For details, refer to Table 8.3

48

1048 DEVICE_STATUS_4

0

Device status For details, refer to Table 8.4

49

1049 DEVICE_STATUS_5

0

Device status For details, refer to Table 8.5

50

1050 DEVICE_STATUS_6

0

Device status For details, refer to Table 8.6

51

1051 DEVICE_STATUS_7

0

Device status For details, refer to Table 8.7

52

1052 DEVICE_STATUS_8

0

Device status For details, refer to Table 8.8

53

1053 SOFTDWN_PROTECT 0x01

AUTO

Defines whether to accept software downloads.

0x01: Unprotected

0x02: Protected

54

1054 SOFTDWN_FORMAT 0x01

AUTO

Selects the software download method.

0x01: Standard

55

1055 SOFTDWN_COUNT

0

Indicates the number of times the internal FlashROM was

erased.

Advertising
This manual is related to the following products: