<Appendix 8. Advanced Diagnostics>

A8-21

IM 01C25R03-01E

Checklist (5/5)

No.

Items

Parameters

Result

Example

10-b

Simulation of Blockage detection

operation

• Close completely the valve for the

side where the alarm of Invalid

Reference Value is not generated.

For the case that the high-pressure side

valve is closed;

• Record the values of VALUE_# after

the certain time, (DIAG_PERIOD ×

DIAG_COUNT), passed.

*: Record the value after checked that

the status is “GOOD”.

VALUE_FDP (Index: 2103)

7.48562e-9

VALUE_FSPH (Index: 2105)

7.14085e-9

For the case that the low-pressure side

valve is closed;

• Record the values of VALUE_# after

the certain time, (DIAG_PERIOD ×

DIAG_COUNT), passed.

*: Record the value after checked that

the status is “GOOD”.

VALUE_FDP (Index: 2103)

7.48562e-9

VALUE_FSPL (Index: 2104)

7.23277e-9

• Record the status of Checkbox in

DIAG_OPTION.

• Check that the alarms status of “B

Blocking” is set.

Note: If the alarm of “Outside Diagnosis

Range” is generated, the valve may

be closed too much tightly. Open

valve a little and record the updated

status of the parameters.

DIAG_OPTION (Index: 2089)

A Blocking

Large Fluctuation of Low Side

Large Fluctuation of High Side

Low Side Blocking

High Side Blocking

B Blocking

Invalid Ref BlkF

Invalid Ref fSPh

Invalid Ref fSPl

Invalid Ref fDP

Outside Diagnosis Range

Reflect Blockage to PV/SV/TV

Status

• Check that the alarm of “B Blocking” is

generated.

DIAG_ERR (Index: 2086)

B Blocking