<2. Handling Cautions>

2-4

IM 01C25R03-01E

● Installation Diagram for Nonincendive

(Division 2 Installation)

Non-Hazardous Location

FM Approved

Associated Nonincendive Field

Wiring Apparatus

Vt or Voc

It or Isc

Ca

La

Hazardous Location

F0203.ai

Terminator

General Purpose

Equipment

Pressure

Transmitter

SUPPLY

Terminator

+

Transmitter

+

Transmitter

+

+

+

Note 1. Installation should be in accordance with

the National Electrical Code ® (ANSI/NFPA

70) Article 500.

Note 2. The configuration of Associated

Nonincendive Field Wiring Apparatus must

be FM Approved.

Note 3. Approved under FNICO Concept.
Note 4. Dust-tight conduit seal must be used

when installed in Class II and Class III

environments.

Note 5. Associated Apparatus manufacturer’s

installation drawing must be followed when

installing this apparatus.

Note 6. No revision to drawing without prior FM

Approvals.

Note 7. Terminator must be FM Approved.
Note 8. The nonincendive field wiring circuit

concept allows interconection of

nonincendive field wiring apparatus with

associated nonincendive field wiring

apparatus, using any of the wiring methods

permitted for unclassified locations.

Note 9. Installation requirements;

Vmax ≥ Voc or Vt

Imax = see note 10.

Ca ≥ Ci + Ccable

La ≥ Li + Lcable

Note 10. For this current controlled circuit, the

parameter (Imax) is not required and need

not be aligned with parameter (Isc) of the

barrier or associated nonincendive field

wiring apparatus.

Note 11. If ordinary location wiring methods are

used, the transmitter shall be connected

to FM Approved associated nonincendive

field wiring apparatus.

Electrical data:

Vmax: 32V

Ci:1.76 nF

Li: 0 µH

● FNICO Rules
The FNICO Concept allows the interconnection of

nonincendive field wiring apparatus to associated

nonincendive field wiring apparatus not specifically

examined in such combination. The criterion for

such interconnection is that the voltage (Vmax),

the current (Imax) and the power (Pmax) which

nonincendive field wiring apparatus can receive and

remain nonincendive, considering faults, must be

equal or greater than the voltage (Uo, Voc or Vt),

the current (Io, Isc or It) and the power (Po) which

can be provided by the associated nonincendive

field wiring apparatus (supply unit). In addition the

maximum unprotected residual capacitance (Ci)

and inductance (Li) of each apparatus (other than

terminators) connected to the Fieldbus must be less

than or equal to 5nF and 20uH respectively.
In each N.I. Fieldbus segment only one active

source, normally the associated nonincendive

field wiring apparatus, is allowed to provide the

necessary power for the Fieldbus system. The

allowed voltage (Uo, Voc or Vt) of the associated

nonincendive field wiring apparatus used to supply

the bus cable must be limited to the range 14Vdc

to 17.5Vdc. All other equipment connected to the

bus cable has to be passive, meaning that the

apparatus is not allowed to provide energy to the

system, except a leakage current of 50 µA for each

connected device. Separately powered equipment

needs galvanic isolation to ensure the nonincendive

field wiring Fieldbus circuit remains passive.