<5. Configuration>

5-2

IM 01C25R03-01E

The node address is used to specify devices for

communication purposes. Because this data is

too long for a PD Tag, the host uses the node

address in place of the PD Tag for communication.

A range of 20 to 247 (or hexadecimal 14 to F7) can

be set. The device (LM device) with bus control

function (Link Master function) is allocated from

a smaller address number (20) side, and other

devices (BASIC device) without bus control function

allocated from a larger address number (247) side

respectively. Place the EJX multivariable transmitter

in the range of the BASIC device. When the EJX

multivariable transmitter is used as Link Master,

place it in the range of the LM device. Set the range

of addresses to be used to the LM device. Set the

following parameters.

Table 5.1

Parameters for Setting Address Range

Symbol

Parameters

Description

V (FUN) First-Unpolled-

Node

Indicates the address

next to the address range

used for the host or other

LM device.

V (NUN) Number-of-

consecutive-

Unpolled-Node

Unused address range

The devices within the address range written

as “Unused” in Figure 5.1 cannot be used on a

Fieldbus. For other address ranges, the range is

periodically checked to identify when a new device

is mounted. Care must be taken to keep the unused

device range as narrow as possible so as to lessen

the load on the Fieldbus.

0xF7

0xF8

0xFB

0xFC

0xFF

V(FUN)

V(FUN)+V(NUN)

LM device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0501.ai

Not used

0x00

0x0F

0x10
0x13

0x14

Bridge device

Figure 5.1

Available Range of Node Addresses

To ensure stable operation of Fieldbus, determine

the operation parameters and set them to the LM

devices. While the parameters in Table 5.2 are to

be set, the worst-case value of all the devices to

be connected to the same Fieldbus must be used.

Refer to the specification of each device for details.

Table 5.2 lists EJX specification values.

Table 5.2

Operation Parameter Values of the EJX

to be Set to LM Devices

Symbol

Parameters

Description and

Settings

V (ST)

Slot-Time

Indicates the time

necessary for immediate

reply of the device. Unit of

time is in octets (256 μs).

Set maximum

specification for all

devices. For EJX, set a

value of 5 or greater.

V (MID)

Minimum-Inter-

PDU-Delay

Minimum value of

communication data

intervals. Unit of time is in

octets (256 μs). Set the

maximum specification

for all devices. For EJX,

set a value of 4 or greater.

V (MRD) Maximum-

Reply-Delay

The worst case time

elapsed until a reply is

recorded. The unit is

Slottime; set the value

so that V (MRD) × V (ST)

is the maximum value

of the specification for

all devices. For EJX, the

setting must be a value of

12 or greater.

5.3 Definition of Combining

Function Blocks

The input/output parameters for function blocks

are combined. As required, they can be combined

with the input of the control block. The setting is

written to the EJX link object. See “Block setting” in

Section 5.6 for the details. It is also possible to read

values from the host at proper intervals instead of

connecting the EJX block output to other blocks.
The combined blocks need to be executed

synchronously with other blocks on the

communications schedule. In this case, change the

EJX schedule according to the following table. The

values in the table are factory-settings.