3 control function basic settings – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 181

Advertising
background image

7-7

M-4659

1

2

3

4

5

6

7

8

Index

Configuring the CX1000/CX2000

7.3

Control Function Basic Settings

Make the basic settings of control function.
To enter settings, click the [Setup] tab then select the settings you wish to enter from the
list that appears on the left of the screen. Or, you can select the items by choosing [Control
Settings] - [Setup Mode].

Control Action

PID Number

Set between 1 and 8. If the number is changed, the program pattern for the program
control option will be initialized.

Control Interval

Set to [250ms], [500ms], or [1s].
However, when [A/D Integrate] under [Scan Interval/Memory] is set to [100ms], you can
only select [1s].

Zone PID

Turn ON or OFF.

Restart Mode

Set to [Continue], [Manual], or [Auto].
With the program control option, the choices are [Continue], [Manual], or [Reset].

Initial PID

Set to [Temp] or [Press+Flow].

6/4LOOP Select (only for CX2000)

Set to 6 or 4 loops.
This selection is only available when the [LOOP] setting in the [System Configuration]
dialog box is set to [6LOOP].

Auto Tuning

Turn ON or OFF.

PV/SP Computation Function (CX Style Number S3 or Later)

Turn the PV/SP computation function ON or OFF. When ON, you can set the PV/SP
equation.

Advertising