Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 229

Advertising
background image

7-55

M-4659

1

2

3

4

5

6

7

8

Index

Configuring the CX1000/CX2000

Alarm

Four alarms (Alarm 1 to 4) can be specified on each channel.

Type

Select H, L, h (dH), l (dL), R (RH), r(RL) T, or t. The selectable alarms vary depending
on the input mode and computation type. For details, see section 7.2 of the CX User’s
Manual (IM 04L31A01-01E or IM 04L31A01-03E)
.

Value

Alarm is generated using the specified value as the boundary. The selectable range of
alarm values varies depending on the input mode and range.

Relay

Select the output relay number or internal switch number for outputting to relay output
or internal switches (Style 3 or later). When not outputting to relays or internal switches,
select NONE.

Detect

Select whether to display alarms (ON) or not to display alarms (OFF) when they occur.
When turned OFF, they are not retained in the alarm summary.

Alarm Delay

An alarm is generated when the measured value stays above or below the specified
value for the specified length of time.

Moving Average

To use the moving average, select the sampling count (2 to 16).

Tag

Use up to 16 alphanumeric characters to specify a tag.
You can select tags instead of channel numbers to be displayed on the screen.
To select whether to display channel names or tag names on the screen, select [AUX] >
[Tag/Channel] on the [Setup] tab.
If you select [Tag] in the [Setup] screen, you can select tag No., tag comment, or tag in
the Data Monitor or Data Viewer.

Zone

You can select the range of the screen in which the waveform of each channel is
displayed.
Specify positions (%) on the display scale for the upper and lower limits.
The conditions for setting the zones are as follows:
• Range: 0% to 100%
The lower limit must be less than the upper limit
• The difference between the lower and upper limits must be at least 5%.

7.8 Measurement Channels Settings

Advertising