Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 60

Advertising
background image

3-44

M-4659

Command setting
• Client command No.

Select from 1 to 16 for the transmitted command numbers to be configured.

• Command

Set the command type.

Settings

Description

Read

Read to the external input channel (16-bit signed integer type) from the server.

R-Math

Read to the communication input data (32-bit floating point type) from the server.

Write

Write the measurement channel (16-bit signed integer type) to the server.

W-Math

Write the measurement channel (32-bit signed integer type) to the server.

[Read] can be selected on DX2000s with the external input channel (/MC1 option) installed.

[R-Math] and [W-Mat] can be selected on models with the computation function (/M1 option)
installed.

• Start channel/End channel (client channels)

Enter the first and last channel numbers of input/output. The range of channels that

you can enter varies depending on the command type as follows:
Read: 201 to 440, R-Math: C01 to C60, Write: 1 to 48, W-Math: 101 to 160

• Connected to (server number)

Select the server number from 1 to 16.

• Register

Set the register number of the server.
For an input register, select in the range of 30001 to 39999 and 300001 to 365536.

For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.

The register numbers you can specify vary depending on the command type. See

section 6/3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual
(IM04L41B01-17E).

• Type

Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or

FLOAT_L.

The register numbers you can specify vary depending on the command type. See

section 6.3 of the DX1000/DX1000N/DX2000 Communication Interface User’s Manual
(IM04L41B01-17E).

3.6 Entering Basic Settings

Advertising