Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 213

Advertising
background image

7-39

M-4659

1

2

3

4

5

6

7

8

Index

Configuring the CX1000/CX2000

• Segment shift action
Set the segment shifting action to [Continue], [Hold] (hold after end of segment),

[Local] (local mode after completing the last segment), or [Reset] (reset mode after
completing the last segment).

Note

When creating the program pattern, data is created so that the segment set to [Local] or [Reset]
is the last segment of program control.

• Wait action
Set the wait action type to [Shift] or [Within]. To disable the wait action, select [Off].

• Wait zone number
Select the wait zone number from [1] to [5]. This item is available only when [Wait

action] is set to [Shift] or [Within].

PV Event

Set the PV Event.

Click this tab

• Loop
Set the target loop number [1] to [6] of the PV event (only selectable loop numbers).

Up to 16 events can be assigned. Select [Off] (initial setting) for the number of the
loops to which the event is not to be assigned.

• Type
Select the type of PV event from the following.
PV high-limit, PV low-limit, deviation high-limit, deviation low-limit, deviation high & low

limit, deviation within high & low limits, SP high-limit, SP low-limit , output high-limit ,
and output low-limit

• Value
Set the value in the following range according to the type of PV event.
PV/SP event: EU (0.0 to 100.0%) of the measurement span
Deviation high-limit event/low-limit event: EUS (–100.0 to 100.0%) of the measurement

span

Deviation high & low limit/within high & low limits: EUS (0.0 to 100.0%) of the

measurement span

Output event: –5.0% to 105.0% of output

PV event display
A bar showing that the PV event was set is displayed in the upper part of the program

pattern display screen.

7.6 Program Control Related Setup Operations

Advertising