Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 194

Advertising
background image

7-20

M-4659

When PV/SP Computation Function is ON

Enter PV or SP related settings.
When the control mode is analog retransmission, the setting menu for that mode is
displayed. See the next page.

PV/SP Computation Function
Select whether to enter settings for PV, PV1, PV2, or SP. Enter PV if the control mode is
single loop control or cascade control, or PV1, PV2 for 2 input switching control. SP can
be entered when the Setup tab’s Internal Loop > [Remote Setting] is set to [Remote].

Mode
Select ON or OFF.
ON: Activates the equation.
OFF: Assigns the following control input channels to the equation.

Loop 1

Loop 2

Loop 3

Loop 4

Loop 5

Loop6

PV

CI01

CI04

CI06

CI09

CI03

CI08

SP

CI02

CI05

CI07

CI10

CI01

CI01

PV(1)

CI01

CI04

CI06

CI09

SP

CI02

CI07

PV1

CI01

CI04

CI06

CI09

PV2

CI02

CI05

CI07

CI10

SP

CI03

CI01

CI08

CI01

PV1

CI01

CI04

CI06

CI09

PV2

CI02

CI05

CI07

CI10

SP

CI01

CI01

CI01

CI01

Control

mode

Single loop

control

Cascade

control

2 input switching

control (4 loops)

2 input switching

control (6 loops)

Equation
Enter the PV/SP equation. If the mode is OFF, the equation cannot be entered.

PV range (PV or PV1)
Set the maximum value, minimum value, decimal place (0–4), and units using 6
alphanumeric characters or less.
Set the max. and min. values between -30000 and 30000 such that max. > min., and
max. - min. ≤ 30000.
PV1 can be set even if the mode is OFF.

Input Switching (PV1)
Set within the PV range. Set the decimal place (0–4), upper limit (U) and lower limit
(L). When setting [Method] to [Range] in [Control Action] under the Setup tab’s Internal
Loop item, and when setting the upper limit (U), lower limit (L), and [Method] to [PV High],
only the upper limit value is set. If you set [Method] to [Signal], the PV Input Switching
setting is not available. This can be set even if the [Mode] is OFF.

7.4 Control Function General Settings