Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 95

Advertising
background image

4-23

M-4659

Displaying Data with the Data V

iewer

1

2

3

4

5

6

7

8

Index

From the Menu Bar

7. Click here (display files for linking).

5. Click here ([Window]-[Link]).

6. The [Link] dialog box opens.

8. Select [Prev] (previous file), [Next] (subsequent file), or [All] (all files).

9. Displays the linked files.

10. Displays the linked files in a different color.

The file extension .ldx is appended to the original file name

Note

When linking and displaying files, make sure that the number of data points after linking does
not exceed 5242880.
In addition, if there is a period over which data does not exist such as when a power failure
occurs, data is counted as if the data is acquired at the given scan interval even during that
period. The scan interval and the maximum period for linking files are indicated below.

Interval

Period

25 ms

36.4 hour

1/8 s

7.5 days

1 s

60.6 days

10 s

606.8 days

For example, if data is captured continuously at a 1/8–second interval and there is a one or
more week long power failure, the data from before and after the power failure cannot be linked
and displayed.

4.5 Linking Files and Saving the Link Settings File