Configuring the CX1000/CX2000

External Loops

Internal loop SP (target set point), A1 (alarm 1 setting), A2 (alarm 2 setting), A3 (alarm

3 setting), A4 (cannot select with UT320, UT321, UT350, or UT420), P (proportional
range), I (integration time), D (differentiation time), OH (upper output limit), OL (lower
output limit), MR (manual reset), H (hysteresis), DR (control action direction), DB (dead
band), PO (preset output), or ETC (others)

Note

When [Connecting Model] in the [Basic Setting] tab of [External Loop] is set to [Other], you can
only select [ETC].

Name
Specify the name of the item using up to 6 alphanumeric characters.

Register
Set the register address in the following ranges.
30001 to 339999, 300001 to 365535, 40001 to 49999, and 400001 to 465535.

Span (Point)
Set the parameter decimal point position.

Span (L)
Set the lower control span value between -30000 to 30000.

Span (U)
Set the upper control span value between -30000 to 30000.

7.3 Control Function Basic Settings