2.4

Parameter setting and configuration

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Service status
If you request the "Send safe data to device" function in the Safe Transfer dialog box via the Send

button, the drive-based safety system changes to the "Service status" which is required for a safe

parameter setting.

Send safe data

( 45)

The service status means:

• The standard stop is active and the drive is safely switched to torqueless operation (STO).
• With safety option 30, the safe inputs are evaluated as OFF state.
• The communication via safety bus is - if possible - active, but passivated.

Supported interfaces for a safe parameter setting
A safe parameter setting with the »Engineer« is supported via the following interfaces:

• Diagnostic interface X70
• CANopen system bus interface

Note!

• The service status is also active if the parameter set in the memory module does not

correspond to the parameter set in the drive-based safety system during the

initialisation.

• The service status can be exited by reinitialising the drive-based safety system, i.e. the

communication via the safety bus is interrupted.