1 profisafe output data, Profisafe output data, 3safe configuration – Lenze E84Dxxxxx User Manual

Page 36

Advertising
background image

3

Safe configuration

3.6

Safety bus

36

Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.6.1.1

PROFIsafe output data

The PROFIsafe output data (control data) is transmitted from the control to the drive-based safety

system.

Control byte
For the PROFIsafe V1 mode only the indicated bits of the PROFIsafe control byte are supported:

[3-1]

Structure of the PROFIsafe control byte in V1 mode

[3-2]

Detailed specification of the control byte in V1 mode

For the PROFIsafe V2 mode only the indicated bits of the PROFIsafe control byte are supported:

[3-3]

Structure of the PROFIsafe control byte in V2 mode

[3-4]

Detailed specification of the control byte in V2 mode

Bit

Name

Value

Meaning

0 STO

0

The STO function is activated.

1 SS1

0

The SS1 function is activated.

9 ES

1

Confirmation is active:

During special operation  motion functions are possible.

11 OMS

0

Normal operation

1

Special operation

16 PS_AIS

01

Activate restart acknowledgement.

The bit must be set for at least one PROFIsafe cycle.

17 PS_AIE

01

Activation of error acknowledgement.

The bit must be set for at least one PROFIsafe cycle.

23 SSE

0

The SSE function is activated.

Unlisted bits are reserved for future extensions and must be transmitted with "0"!

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

-

-

-

activate_FV

-

-

-

-

Bit coding of control byte

Bit

Name

Value

Meaning

4 activate_FV

1

The PROFIsafe output data is passivated.

-

0

Reserved for future extensions.

Assignment

Bit

Byte

7

6

5

4

3

2

1

0

4

-

-

Toggle_h

activate_FV

-

R_cons_nr

-

-

Bit coding of control byte

Bit

Name

Value

Meaning

2 R_cons_nr

1

Reset of the consecutive number.

4 activate_FV

1

The PROFIsafe output data is passivated.

5 Toggle_h

1/0

Change increases the consecutive number.

-

0

Reserved for future extensions.