C15003 | command status, C15010 | parameter set status, C15011 | parameter crc – Lenze E84Dxxxxx User Manual

Page 52: 7parameter reference

Advertising
background image

7

Parameter reference

7.1

Parameter list | C15003

52

Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C15003

C15010

C15011

C15012

Parameter | Name:

C15003 | Command status

Data type: UNSIGNED_16

Index: 9572

d

= 2564

h

Status of the current command

• The command is repeated in the high byte.

• In the low byte the status is displayed:

0x00: No command

0x01: Command executed

0x02: Password invalid

0x03: Command in process

0x04: Command not known

0x05: Command error

Display range

(min. value | unit | max. value)

0

2309

Read access  Write access  CINH  PLC STOP  No transfer Scaling factor: 1

Parameter | Name:

C15010 | Parameter set status

Data type: UNSIGNED_8

Index: 9565

d

= 255D

h

Selection list

(read only)

0 No parameter set
1 Valid parameter set
2 Read error - memory module
3 Unequal parameter set
4 CRC error
5 Version error
6 Format error
7 Plausibility error
8 Assignment error
9 Local read error

10 Communication error standard

device

Read access  Write access  CINH  PLC STOP  No transfer Scaling factor: 1

Parameter | Name:

C15011 | Parameter CRC

Data type: UNSIGNED_32

Index: 9564

d

= 255C

h

Parameter checksum (CRC = Cyclic Redundancy Code)
Display range

(min. value | unit | max. value)

0

4294967295

Subcodes

Information

C15011/1

CRC safety system

C15011/2

CRC memory module

Read access  Write access  CINH  PLC STOP  No transfer Scaling factor: 1

Parameter | Name:

C15012 | Password

Data type: UNSIGNED_32

Index: 9563

d

= 255B

h

This code is for device-internal use only and must not be written to by the user!