3
Safe configuration
3.6
Safety bus
40
Lenze · 8400 protec · Drive-based safety · Software Manual · DMS 2.4 EN · 05/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PROFIsafe parameter
These PROFIsafe parameters and contents are supported:
[3-10] Supported PROFIsafe parameters
Diagnostic messages
Faulty configurations of the PROFIsafe parameters are reported to the safety PLC with a diagnostic
telegram (communication manual PROFINET).
Diagnostic information
GSDML file
All information on the configuration of the PROFINET system is contained in the GSDML file. Thus,
the integration is easy and user-friendly.
PROFIsafe parameter
Name
Description
Valid contents
F_Source_Add
PROFIsafe source address of the safety PLC
0x01 ... 0xFFFE
F_Dest_Add
PROFIsafe target address of the safety system
DIP switch:
Code:
0x01 ... 0x03FF
0x01 ... 0xFFFE
F_WD_Time
PROFIsafe monitoring time of the safety system
110 ... 65535 ms
F_Check_SeqNr
Check of the sequence no. in CRC
V1 mode:
V2 mode:
0
not relevant
F_Check_iPar
Check of the iParameters CRC3 in CRC
0
F_SIL
Supported SIL (Safety Integrity Level)
SIL1:
SIL2:
SIL3:
0
1
2
F_CRC_Length
Length of CRC
V1-mode/2-byte-CRC:
V2-mode/3-byte-CRC:
1
0
F_Block_ID
Identification of the parameter type
0
F_Par_Version
Version of the safety layer
V1 mode:
V2 mode:
0
1
F_Par_CRC
cyclic CRC
is calculated
Error number
Description
64
The set PROFIsafe target address does not comply with the F_Dest_Add parameter.
65
The F_Dest_Add parameter has the invalid value 0x0000 or 0xFFFF
66
The F_Source_Add parameter has the invalid value 0x0000 or 0xFFFF.
67
The F_WD_Time parameter has the invalid value 0 ms.
68
The F_SIL parameter does not have the valid value 0 ... 2.
69
The F_CRC_Length parameter does not have the valid value 1.
70
The version of the PROFIsafe parameter set is wrong.
71
CRC1 error