Dpi alarm object, Class code, Instances – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual
Page 103: Class attributes, C-17

CIP Objects
C-17
20-COMM-R Remote I/O Adapter User Manual
Publication 20COMM-UM004D-EN-P
DPI Alarm Object
Class Code
Products such as PowerFlex drives use this object for alarms or warnings.
Adapters do not support this object.
Instances
The number of instances depends on the maximum number of alarms
supported by the queue. The maximum number of alarms can be read in
Instance 0, Attribute 2.
Class Attributes
Hexadecimal Decimal
0x98
152
Instances (Hex.)
(Dec.)
Device
Example
Description
0x0000…0x3FFF
0…16383
Host
0
Class Attributes (Drive)
Only host devices can have alarms.
1
Most Recent Alarm
2
Second Most Recent Alarm
…
…
Attribute ID Access Rule
Name
Data Type
Description
1
Read Only
Class Revision
WORD
Revision of object
2
Read Only
Number of
Instances
WORD
Maximum number of alarms that the
device can record in its queue
3
Write
Alarm Command
Write
BYTE
0 = No Operation
1 = Clear Alarm
2 = Clear Alarm Queue
3 = Reset Device
4
Read Only
Fault Data List
STRUCT of:
BYTE
BYTE
WORD[n]
Reserved
5
Read Only
Number of
Recorded Alarms
WORD
Number of alarms in the queue. A ‘0’
indicates the alarm queue is empty.