Dpi alarm object, Class code, Instances – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 103: Class attributes, C-17

Advertising
background image

CIP Objects

C-17

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

DPI Alarm Object

Class Code

Products such as PowerFlex drives use this object for alarms or warnings.
Adapters do not support this object.

Instances

The number of instances depends on the maximum number of alarms
supported by the queue. The maximum number of alarms can be read in
Instance 0, Attribute 2.

Class Attributes

Hexadecimal Decimal
0x98

152

Instances (Hex.)

(Dec.)

Device

Example

Description

0x0000…0x3FFF

0…16383

Host

0

Class Attributes (Drive)

Only host devices can have alarms.

1

Most Recent Alarm

2

Second Most Recent Alarm

Attribute ID Access Rule

Name

Data Type

Description

1

Read Only

Class Revision

WORD

Revision of object

2

Read Only

Number of

Instances

WORD

Maximum number of alarms that the

device can record in its queue

3

Write

Alarm Command

Write

BYTE

0 = No Operation

1 = Clear Alarm

2 = Clear Alarm Queue

3 = Reset Device

4

Read Only

Fault Data List

STRUCT of:

BYTE

BYTE

WORD[n]

Reserved

5

Read Only

Number of

Recorded Alarms

WORD

Number of alarms in the queue. A ‘0’

indicates the alarm queue is empty.