Troubleshooting

6-3

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

NET A Status Indicator

This red/green bicolor LED indicates the status for the Remote I/O network
connection as shown in the table below.

Viewing Adapter Diagnostic

Items

If you encounter unexpected communications problems, the adapter’s
diagnostic items may help you or Rockwell Automation personnel
troubleshoot the problem. Adapter diagnostic items can be viewed with any
of these drive configuration tools:

• LCD PowerFlex 7-Class HIM (Diagnostics/Device Items)

• Connected Components Workbench software, version 1.02 or later

• DriveExplorer software, version 2.01 or later

• DriveExecutive software, version 3.01 or later

Using the HIM to View Adapter Diagnostic Items

Status

Cause

Corrective Actions

Off

The adapter is not powered or is not properly

connected to the network.

• Securely connect the adapter to the drive using the Internal

Interface (ribbon) cable and to the network using a Remote I/O

cable.

• Correctly connect the Remote I/O network cable to the 3-pin

Remote I/O plug.

• Configure the adapter to use the baud rate at which the

network is operating.

• Configure the adapter to use a unique rack address on the

Remote I/O network.

• Apply power to the drive and network.
• Apply power to the controller.

Flashing Green The adapter is properly connected but is not

transferring I/O over the network.

• Verify that the scanner is in Run mode.
• Verify that the scanner is using the correct rack size for the

adapter.

• Verify that the adapter is configured for the correct rack size.

Steady Green

The adapter is properly connected and is

communicating with the scanner on the network.

No action required.

Step

Example Screen

1. Access parameters in the adapter.

See

Using the PowerFlex 7-Class HIM to Access Parameters on

page 3-2

.

2. Press the

or

key to scroll to

Diagnostics.

3. Press the

(Enter) key to display the Diagnostics menu in

the adapter.

4. Repeat steps 2 and 3 to enter the

Device Items option.

5. Press the

or

key to scroll through the items.

Main Menu:

Diagnostics

Parameter

Device Select

Device Item #

3

Reference

Advertising