Setting the last rack, Setting the rack size, Setting the last rack -5 setting the rack size -5 – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 31

Advertising
background image

Configuring the Adapter

3-5

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Setting the Last Rack

If adapter Configuration DIP Switches SW7 and SW8 (

Figure 2.2

) are both

set to ‘On’, the value of Parameter 26 - [Last RIO Rack] notifies the
controller that this device is the last device on a specified rack. This
parameter must be set to ‘1’ (Enabled) if the drive is the last device on a
rack address that uses a PLC-2 controller. We recommend that you set this
parameter to ‘1’ (Enabled) whenever a device is the last device on a rack.

1. Set the value of Parameter 26 - [Last RIO Rack] to the desired state.

2. Reset the adapter (see

Resetting the Adapter on page 3-8

).

Setting the Rack Size

If adapter Configuration DIP Switches SW7 and SW8 (

Figure 2.2

) are both

set to ‘On’, the value of Parameter 27 - [Rack Size] determines the rack
size. With the 20-COMM-R adapter, you can use a 1/4 or 1/2 size rack. This
I/O is the Discrete I/O. For more information about using I/O, see

Chapter 4

,

Using Discrete and Block Transfer I/O

.

1. Set the value of Parameter 27 - [Rack Size] to the size required for your

application.

2. Reset the adapter (see

Resetting the Adapter on page 3-8

).

Port 5 Device
20-COMM-R
Parameter #: 26

Last RIO Rack

0

Disabled

Value

Last Rack

0

Disabled (default)

1

Enabled

TIP: Additional I/O, such as Reference/Feedback and Datalinks, can be
transmitted using the Block Transfer I/O image.

Port 5 Device
20-COMM-R
Parameter #: 27

Rack Size

0

1/4 Rack

Value

Rack Size

0

1/4 (default)

1

1/2