4-10

Using Discrete and Block Transfer I/O

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

In this example, the Parameter 10 - [Elapsed Run Time] value of 6553.9 Hrs
is read as ‘6553.9’ in Datalink A1 Out (Parameter 310) and Datalink A2
Out (Parameter 311).

Conversion Example:

Parameter 010 - [Elapsed Run Time]

= 6553.9 Hrs

MSW = 0001

hex

= 0001

binary

= 2

16

= 65536

LSW = 0003

hex

=3

Engineering Value = 65536 + 3 = 65539
Parameter 10 Displayed Value = 6553.9 Hrs

Regardless of the Datalink combination, Datalink x1 Out will always
contain the LSW and Datalink x2 Out will always contain the MSW. In the
following example, the PowerFlex 70 drive parameter 242 - [Power Up
Marker] contains a value of 88.4541 hours.

Conversion Example:

Parameter 242 - [Power Up Marker]

= 88.4541 hours

MSW = 000D

hex

= 1101

binary

= 2

19

+ 2

18

+ 2

16

= 851968

LSW = 7F3D

hex

= 32573

Engineering Value = 851968 + 32573 = 884541
Parameter 242 Displayed Value = 88.4541 Hrs

Datalink

Word

Parameter

Data (Hex)

A1 Out

LSW

10

0003

A2 Out

MSW

10

0001

Datalink

Word

Parameter

Data (Hex)

A2 Out

MSW

242

000D

B1 Out

LSW

242

7F3D