CIP Objects

C-11

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

The data in this example is for a Get_Attributes_Scattered of PowerFlex 70
parameters 1 - [Output Freq], 3 - [Output Current] and 6 - [Output Voltage]
from a device at node address 1.

Request Data for Get_Attributes_Scattered

Response Data for Get_Attributes_Scattered

Address

Value (hex) Description

Page

N30:0

001C

Length = 28 bytes (1C hex)

5-3

N30:1

0081

Port = 00, 0 x 81

5-3

N30:2

004B

0 x 00, Service = Get_Attributes_Scattered

5-3

N30:3

0093

Class = 93 (DPI Parameter Object)

C-5

N30:4

0000

Instance = Class Attributes (drive)

C-5

N30:5

0000

Attribute (not used for this service)

C-5

N30:6

0001

Parameter Number 1

n/a

N30:7

0000

Pad Word

N30:8

0000

Pad Word

N30:9

0003

Parameter Number 3

N30:10

0000

Pad Word

N30:11

0000

Pad Word

N30:12

0006

Parameter Number 6

N30:13

0000

Pad Word

N30:14

0000

Pad Word

Address

Value (hex) Description

Page

N30:70

0014

Length = 20 bytes (14 hex)

5-4

N30:71

0000

Status Code = 00 (successful transaction)

5-4

Status Size = 00

5-4

N30:72

0000

Status Information = 0

5-4

N30:73

0001

Parameter Number 1

n/a

N30:74

0258

Value = 600 (258 hex) = 60.0 Hz

N30:75

0000

N30:76

0003

Parameter Number 3

N30:77

0001

Value = 1 (1 hex) = 0.1A

N30:78

0000

N30:79

0006

Parameter Number 6

N30:80

0864

Value = 2148 (864 hex) = 214.8V AC

N30:81

0000