Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 25

Advertising
background image

Installing the Adapter

2-9

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Figure 2.8 Drive and Adapter Status Indicators (location on drive may vary)

For more details on status indicator operation, see

page 6-2

and

page 6-3

.

Table 2.A Drive and Adapter Start-Up Status Indications

Item Name

Color

State

Description

Drive STS Indicator

STS

(Status)

Green

Flashing

Drive ready but not running, and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing,

drive stopped

An inhibit condition exists – the drive cannot be

started. Check drive Parameter 214 - [Start Inhibits].

Flashing,

drive running

An intermittent type 1 alarm condition is occurring.

Check drive Parameter 211 - [Drive Alarm 1].

Steady,

drive running

A continuous type 1 alarm condition exists. Check

drive Parameter 211 - [Drive Alarm 1].

Red

Flashing

A fault has occurred.

Steady

A non-resettable fault has occurred.

Adapter Status Indicators

PORT

Green

Flashing

Normal operation. The adapter is establishing an I/O

connection to the drive. It will turn steady green or red.

Steady

Normal operation. The adapter is properly connected

and communicating with the drive.

MOD

Green

Flashing

Normal operation. The adapter is operating but is not

transferring I/O data to a controller.

Steady

Normal operation. The adapter is operating and

transferring I/O data to a controller.

NET A

Green

Flashing

The adapter is properly connected, but the controller is

resetting, in test mode, in program mode, or not

properly configured to communicate with the adapter.

Steady

Normal operation. The adapter is properly connected

and communicating on the network.

NET B

Not used by Remote I/O adapter.

STS

PORT

MOD

NET A

NET B