Block Transfer I/O Image

The Block Transfer I/O image is a Block Transfer message that contains
eighteen 16-bit words. It reserves two words for the Reference/Feedback
and four words for each Datalink (in case 32-bit values are used).

Figure 4.3 Block Transfer I/O Image for 16-Bit Reference and Datalinks

Figure 4.4 Block Transfer I/O Image for 32-Bit Reference and Datalinks

LSW = Least Significant Word (bits 0…15)

MSW = Most Significant Word (bits 16…31)

Block Transfer I/O requests must be eighteen (18) words or fewer. If a
Reference or Datalink In field is not configured to be used by the adapter,
any value placed in the field will be ignored by the adapter. If a Datalink
Out field is not configured to be used by the adapter, the value of that field is
undefined. The Feedback field will always contain the Feedback from the

Word 0

1

Reference

Not Used

Feedback

0

2

3

4

5

Datalink In A1

Not Used

Datalink In A2

Not Used

Datalink Out A1

0

Datalink Out A2

0

6

7

8

9

Datalink In B1

Not Used

Datalink In B2

Not Used

Datalink Out B1

0

Datalink Out B2

0

10

11

12

13

Datalink In C1

Not Used

Datalink In C2

Not Used

Datalink Out C1

0

Datalink Out C2

0

14

15

16

17

Datalink In D1

Not Used

Datalink In D2

Not Used

Datalink Out D1

0

Datalink Out D2

0

Word 0

1

Reference (LSW)

Reference (MSW)

Feedback (LSW)

Feedback (MSW)

2

3

4

5

Datalink In A1 (LSW)

Datalink In A1 (MSW)

Datalink In A2 (LSW)

Datalink In A2 (MSW)

Datalink Out A1 (LSW)

Datalink Out A1 (MSW)

Datalink Out A2 (LSW)

Datalink Out A2 (MSW)

6

7

8

9

Datalink In B1 (LSW)

Datalink In B1 (MSW)

Datalink In B2 (LSW)

Datalink In B2 (MSW)

Datalink Out B1 (LSW)

Datalink Out B1 (MSW)

Datalink Out B2 (LSW)

Datalink Out B2 (MSW)

10

11

12

13

Datalink In C1 (LSW)

Datalink In C1 (MSW)

Datalink In C2 (LSW)

Datalink In C2 (MSW)

Datalink Out C1 (LSW)

Datalink Out C1 (MSW)

Datalink Out C2 (LSW)

Datalink Out C2 (MSW)

14

15

16

17

Datalink In D1 (LSW)

Datalink In D1 (MSW)

Datalink In D2 (LSW)

Datalink In D2 (MSW)

Datalink Out D1 (LSW)

Datalink Out D1 (MSW)

Datalink Out D2 (LSW)

Datalink Out D2 (MSW)

Block Transfer Write

Block Transfer Read

Block Transfer Write

Block Transfer Read