Port status indicator, Mod status indicator, Port status indicator -2 mod status indicator -2 – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 76

Advertising
background image

6-2

Troubleshooting

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

PORT Status Indicator

This red/green bicolor LED indicates the status of the adapter’s connection
to the drive as shown in the table below.

MOD Status Indicator

This red/green bicolor LED indicates the status of the adapter as shown in
the table below.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly

connected to the drive.

• Securely connect the adapter to the drive using the Internal

Interface (ribbon) cable.

• Apply power to the drive.

Flashing Red

The adapter is not receiving a ping message from the

drive.

• Verify that cables are securely connected and not damaged.

Replace cables if necessary.

• Cycle power to the drive.

Steady Red

The drive has refused an I/O connection from the

adapter.

Another DPI peripheral is using the same DPI port as

the adapter.

Important: Cycle power to the drive after making any of the

following corrections:

• Verify that all DPI cables on the drive are securely connected

and not damaged. Replace cables if necessary.

• Verify that the DPI drive supports Datalinks.
• Configure the adapter to use a Datalink that is not already

being used by another peripheral.

Steady

Orange

The adapter is connected to a product that does not

support Allen-Bradley DPI communications.

Connect the adapter to a product that supports Allen-Bradley

DPI communications (for example, a PowerFlex 7-Class drive).

Flashing

Green

The adapter is establishing an I/O connection to the

drive.

• No action required. Normal behavior if no DPI I/O is enabled.

This status indicator will turn steady green or red.

• Verify Parameter 12 - [DPI I/O Cfg] settings.

Steady Green

The adapter is properly connected and is

communicating with the drive.

No action required.

Status

Cause

Corrective Action

Off

The adapter is not powered or is not properly

connected to the drive.

• Securely connect the adapter to the drive using the Internal

Interface (ribbon) cable.

• Apply power to the drive.

Flashing Red

The adapter has failed the firmware test or the Rack

Address Rotary Switch setting is invalid.

The adapter firmware is being updated.

• Verify that the Rack Address Rotary Switch setting is

between 0 and 77 octal or, if all hardware switches are

disabled,

Parameter 3 - [RIO Addr Cfg] is between 0 and 63

decimal.

• Clear faults in the adapter.
• Cycle power to the drive.
• If cycling power does not correct the problem, the adapter

parameter settings may have been corrupted. Reset defaults

and reconfigure the adapter.

• If resetting defaults does not correct the problem, update the

adapter with the latest firmware revision.

Steady Red

The adapter has failed the hardware test.

• Cycle power to the drive.
• Replace the adapter.

Flashing

Green

The adapter is operational, but is not transferring

I/O data.

• Place the scanner in RUN mode.
• Program the controller to recognize and transmit I/O to the

adapter.

• Configure the adapter for the program in the controller.
• Normal behavior if no DPI I/O is enabled.

Steady Green

The adapter is operational and transferring I/O data.

No action required.

Advertising